Problem
The timer does not set a Config I/O
output.
'Delayer' does not trigger an
A
'Action' .
12.4.7
Brief explanation of selected functions
Time event (trigger)
Actions
Initialisation
Outputs
Inputs
Delayer
Possible cause of fault
Config I/O was not configured as
"Timer I/O" - "Input" in the
'Menu / Information è Settings
Inputs/Outputs è ...' menu.
è
Different delay times have been
defined for the same
'Delayer' but this
delayer is stopped and becomes inac‐
tive after the shortest delay time.
An event can be triggered either time-dependent or event-controlled.
1 - Time events (really time-dependent) are processed precisely to the
minute.
'Init' ) is executed at the start of the program ( 'Timer
2 - Initialisation (
Activation è active' or when mains voltage is connected) to obtain
è
a defined status of the system.
3 - "Config I/O" inputs can trigger something if the input potential
changes from 1 to 0 or with a falling edge or if the potential-free con‐
tact is closed.
4 - Delayers can trigger an action as soon as their time has expired.
'Actions' which the timer executes as soon as a 'time
These are the
event' has occurred.
When
'Activation' is set to 'active' , the timer software generates the state
of the pump which the pump would have precisely had at this time if it
would have been set to
This does not relate to delayed, linked actions.
Using the initial commands (
grammed. Initial commands have priority over time commands.
Those relays which were connected with the relay option are designated
as outputs. Up to 2 relays can be fitted.
Pins 1 - 3 of the "Config I/O" terminal can be inputs and outputs. That can
be programmed.
Pins 1 - 3 of the "Config I/O" terminal can be inputs and outputs. That can
be programmed.
Delayers are started event- or time-controlled. Upon expiry of the delay
time, the delayer itself can trigger any actions.
Remedy
Configure Config I/O as a "Timer" -
'Menu / Information
"Input" in the
Settings è Inputs/Outputs è ...'
è
menu.
Create a further
longer delay time.
'active' without any interruption.
'Init' ), a defined switch-on state can be pro‐
'Menu'
Set up /
'Delayer' for the
73