Functional description
LED display
Operating display

6.7 Hierarchy of operating modes, functions and fault statuses

22
Colour
lit
green
The pump is ready for
operation
The different operating modes, functions and fault statuses have a dif‐
ferent impact on whether and how the pump reacts.
The following list shows the order:
1. - Priming
2. - Stop
3. - Error, Pause
4. - Auxiliary capacity
5. - Manual, Analog, Contact, Batch, Fieldbus
Comments:
re 1. - "Priming" can take place in any pump mode (providing it is
working).
re 2. - "Stop" stops everything.
re 3. - "Error", and "Pause" stop everything apart from "Priming".
re 4. - "Auxiliary capacity" always has priority over the capacity specified
by an operating mode listed under 5 or the fieldbus.
lights up
-
During every revolution:
Capacity greater than 10
l / h
During every 1/2 revolu‐
tion:
Capacity less than 10 l /
h
During every 1/8 revolu‐
tion:
Capacity less than 1 l / h
every 4 s:
Capacity less than 500
ml / h
flashes
-
-
-
-
-