Siemens SINAMICS S120 Commissioning Manual page 54

Canopen interface
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Add infeed
1.20 Parameters, save, restore factory settings
Restoring the factory setting of the parameters (object 1011 hex)
● Subindex 0: (1011.0):
● Subindex 1: (1011.1):
original factory setting.
This corresponds to writing a "1" to drive parameter p0976.
● Subindex 2: (1011.2):
By writing the ASCII character sequence "daol" - which corresponds to the hexadecimal
value "64 61 6F 6C" - to this subindex, only the communication objects (objects of the
number group 1000hex - 1FFFhex) of the drive are reset to their factory setting.
● Subindex 3: (1011.3):
By writing the ASCII character sequence "daol" - which corresponds to the hexadecimal
value "64 61 6F 6C" - to this subindex, only the application objects (objects of the number
group 6000hex - 9FFFhex) of the drive are reset to their factory setting.
When reading subindices 1-3, a value of "1" is obtained, which has the following
significance: The device sets the parameters back to their factory setting via write access of
the object.
See also
Control Unit communication objects independent of the drive (Page 129)
54
The number of subindices of this object are shown in this subindex.
By writing the ASCII character sequence "daol" - which corresponds to the hexadecimal
value "64 61 6F 6C" - to this subindex, all of the drive parameters are reset to their
Commissioning Manual, (IH2), V2.6, 10/2008 Edition, 6SL3097-2AA00-0BP3