Environmental Tests
Radiated Emissions
Conducted Emissions
ESD immunity
(Performance Criteria B)
Radiated RF immunity
(Performance Criteria A)
EFT/B immunity
(Performance Criteria B)
Surge transient immunity
(Performance Criteria B)
Conducted RF immunity
(Performance Criteria A)
Magnetic Field
(Performance Criteria A)
AC Mains Voltage Dips, Interruptions
and Variations
User's Manual Pub. 0300308-02 Rev. A
Table 1-2 EMC Specification Table
Test Level Limits
(Enclosure) Class A, 30 MHz – 1 GHz
Group 1, Class A (AC Mains), 150 kHz – 30 MHz
6 kV Indirect (Coupling Plate)
6 kV Contact Discharge (to points of initial contact)
8 kV Air Discharge (to points of initial contact)
10 V/M with 1 kHz sine-wave 80% AM from 80...6000 MHz
10 V/M with 200 Hz square-wave 50% Pulse 100% AM at
900 MHz
10 V/M with 200 Hz square-wave 50% Pulse 100% AM at
1890 MHz
Signal Ports:
± 2 kV at 5 kHz for 5 minutes, Criteria B
Power Ports:
± 2 kV at 5 kHz for 5 minutes, Criteria B
Signal Ports:
± 2 kV line-earth {CM}at 2Ω on shielded ports
Power Ports
±2 kV CM at 12 Ω
±1 kV DM at 2 Ω
10 V RMS with 1 kHz sine wave 80% AM from 150
kHz...80 MHz on signal and power ports
30 Arms/m
Follow the 61000-4-11.