General Specifications - Mitsubishi Electric MELSEC-A Series User Manual

Hide thumbs Also See for MELSEC-A Series:
Table of Contents

Advertisement

3. GENERAL SPECIFICATIONS
- - - - - - - - - - - - - - - - - - - - MELSEC-A
3.
GENERAL SPECIFICATIONS
Table 3.1 shows the common specification of various modules used.
Table 3.1 General SpecificatIons
Item
Specification
Operating
ambient
o
to 55°C
temperature
Storage ambient
-20
to
75°C
temperature
Operating
10
to
90% RH, non-condensing
ambient humidity
Storage ambient
10
to
90% RH, non-condensing
humidity
Frequency
Acceleration
AmplRude
Sweep Count
Vibration
Conforms to
10 10 55Hz
0.075 mm
resistance
*JIS C 0911
-
(0.003 in)
10 times
*(1 octave/minute)
5510150 Hz
1 9
-
Shock resistance
Conforms to JIS C 9012 (10 9 x 3 times in 3 directions)
Noise durability
By
noise simulator of
1500 Vpp
noise voltage,
1
ps noise
width
and
25
to
60
Hz noise
frequency
Dielectric
1500 VAC for 1 minute across AC externals and ground
withstand
voltage
500 VAC for 1 minute across DC external terminals and ground
Insulation
5
Me
of larger by 400 VOC insulation resistance tester across
resistance
AC external terminals and ground
Grounding
Class 3 grounding: grounding is not required when it is impossible
Operating
Free of corrosive gases. Oust should be minimal.
ambient
Cooling method
Self-cooling
IREMARKSI
(1) One octave marked
*
indicates a change from the initial frequency to double or half
frequency. For example, any of the changes from 10Hz to 20 Hz, from 20 Hz to 40 Hz, from
40 Hz to 20 Hz, and 20 Hz to 10Hz are referred to as one octave.
(2) Since a varistor is provided between AC and LG, do not apply a voltage of 400 V or higher
between AC and LG.
(3) Disconnect grounding of FG and LG before applying the maximum allowable voltage to the
A66PC. 00 not connect leads to FG and LG when applying the maximum allowable voltage
since they are shorted in the module.
Note:
*
JIS : Japanese Industria/ Standard
3-1