4. A2CCPU
- - - - - - - - - - - - - - - - - - - - MELSEC·A
I
4.4
Parameter Setting Range
Parameters are used to allocate user memory area or the use range of the
functions.
The parameter data is stored in the first 3K bytes in the user memory area.
(1) Default values
Each parameter has a default value as indicated in Table 4.9.
It is not necessary to change parameter data; programs can be run with
default settings.
(2)
Changing parameter setting
Parameter settings can be changed in the range as indicated in Table
4.9 to meet specific operation needs. A peripheral device should be
used to change the setting.
See the Operation Manual for the peripheral device to be used for the
procedure to set the parameter data.
IREMARKl
(1) Conversion of main sequence program capacity, file register capacity and comment
capacity from "steps" and "points" to "bytes" is described below.
Item
Setting Unit.
Number of Byte.
Main sequence program capacity
1K
steps
2K bytes
File register capacity
1K
points
2K bytes
Comment capacity
64 points
1K byte
(2) When comment capacity is set with a peripheral device, 1K byte area is automatically taken
in addition to the setting; the comment capacity displayed is, therefore, 1K byte larger than
the set value.
Table 4.9 Parameter Setting Range
~ t .
Default
Peripheral Device.
Value
Setting Range
Ref.r to
Item
PU
GPP HGP PHP
Main sequence program capacity
6K steps
1
to 8K steps
0
0
0
0
(1K step increments)
File register capacity
None
1 to 4K points
0
0
0
0
(1K point increments)
Comment capacity
None
o to 4032 points
*
1
-
0
0
0
4.4.1
(64 point increments)
Memory capacity
0/8 to 12K bytes
Status latch
Data memory
None
NolYes
-
0
0
0
File register
Nerves (2 to BK bytes)
4-49