Chapter 4 General Specifications - Mitsubishi Electric MELSEC iQ-F Series User Manual

Programmable
Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

4
GENERAL SPECIFICATIONS
This chapter describes the common specifications for the modules to be used.
Item
Operating
FX5S CPU module
ambient
FX5UJ CPU module
*1
temperature
FX5U CPU module
FX5UC CPU module
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
*5*6
Vibration resistance
*5
Shock resistance
*7
Noise durability
Grounding
Working atmosphere
*9
Operating altitude
Installation location
*11
Overvoltage category
*12
Pollution degree
*1 The simultaneous ON ratio of available programmable controller inputs or outputs changes with respect to the ambient temperature, For
details, refer to the following.
Page 98 Input/Output Derating Curve
*2 The operating ambient temperature is 0 to 55 for products manufactured before June 2016. For details on intelligent function
modules, refer to manuals of each product.
*3 In the case where operating ambient temperature is lower than 0, the specifications are different from the above description. For
details, refer to Page 60 Precautions for operating ambient temperature.
*4 When used in a low-temperature environment, use in an environment with no sudden temperature changes. When there are sudden
temperature changes because of opening/closing of the control panel or other reasons, condensation may occur, which may cause a
fire, fault, or malfunction. Furthermore, use an air conditioner in dehumidifier mode to prevent condensation.
*5 The criterion is shown in IEC 61131-2.
*6 When the system has equipment which specification values are lower than above mentioned vibration resistance specification values,
the vibration resistance specification of the whole system is corresponding to the lower specification.
*7 When using the FX5 safety extension modules under the severe noise environment, implement external noise countermeasures with a
surge absorber and ferrite core.
*8 For grounding, refer to Page 171 Grounding
*9 The programmable controller cannot be used at a pressure higher than the atmospheric pressure to avoid damage.
*10 The programmable controller is assumed to be installed in an environment equivalent to indoor.
*11 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within premises. Category  applies to equipment for which electrical power is supplied from
fixed facilities. The surge voltage withstand level for up to the rated voltage of 300V is 2500V.
*12 This index indicates the degree to which conductive material is generated in the environment in which the equipment is used. Pollution
level 2 is when only non-conductive pollution occurs. Temporary conductivity caused by condensation must be expected occasionally.
4 GENERAL SPECIFICATIONS
82
Specifications
0 to 55, non-freezing
*2*3
-20 to 55, non-freezing
-25 to 75, non-freezing
*4
5 to 95%RH, non-condensation
5 to 95%RH, non-condensation
Frequency
Installed on DIN rail
5 to 8.4Hz
8.4 to 150Hz
Direct installing
5 to 8.4Hz
8.4 to 150Hz
147m/, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
By noise simulator at noise voltage of 1000Vp-p, noise width of 1s and period of 30 to 100Hz
Class D grounding (grounding resistance: 100 or less) <Common grounding with a heavy electrical system is not
*8
allowed.>
Free from corrosive or flammable gas and excessive conductive dust
0 to 2000m
*10
Inside a control panel
 or less
2 or less
Acceleration
Half amplitude
1.75mm
4.9m/
3.5mm
9.8m/
Sweep count
10 times each in X,
Y, Z directions
(80min in each
direction)