Parameter Description
[23]
Set-up select bit 0
[24]
Set-up select bit 1
[32]
Pulse input
[34]
Ramp bit 0
[36]
Mains failure inverse
[37]
Fire mode
[52]
Run Permissive
[53]
Hand start
[54]
Auto-start
[55]
DigiPot Increase
[56]
DigiPot Decrease
[57]
DigiPot Clear
[60]
Counter A (up)
[61]
Counter A (down)
[62]
Reset Counter A
4-56
Selects one of the four set-ups. Set par. 0-10 to Multi Set-up.
Same as Set-up select bit 0 [23].
(Default Digital input 32)
Select Pulse input when using a pulse sequence as either reference or
feedback. Scaling is done in par. group 5-5*.
Select which ramp to use. Logic "0" will select ramp 1 while logic "1"
will select ramp 2.
Select to activate function selected in par.14-10
ure is active in the Logic "0" situation.
A signal applied will put the adjustable frequency drive into fire mode
and all other commands will be disregarded. See 24-0*
The input terminal, for which the Run permissive has been programmed
must be logic "1" before a start command can be accepted. Run permis-
sive has a logic 'AND' function related to the terminal which is program-
START
Jog
med for
[8],
[14] or
order to start running the motor, both conditions must be fulfilled. If Run
Permissive is programmed on multiple terminals, Run permissive needs
only be logic '1' on one of the terminals for the function to be carried out.
The digital output signal for Run Request (
put
[20]) programmed in par. 5-3*, or par. 5-4*, will not be affected by
Run Permissive.
NOTE: If no Run Permissive signal is applied but either Run, Jog or Freeze
commands is activated, the status line in the display will show either Run
Requested, Jog Requested or Freeze Requested.
A signal applied will put the adjustable frequency drive into hand mode
Hand On
as if button
on the keypad has been pressed and a normal stop
command will be overridden. If disconnecting the signal, the motor will
stop. To make any other start commands valid, another digital input must
Auto Start
be assign to
and a signal applied to this. The
Auto On
buttons on the keypad has no impact. The
Hand Start
keypad will override
Auto On
or
button to make
Hand Start
signal on neither
of any normal Start command applied. If signal applied to both
Start
Auto-Start
and
, the function will be
button on the keypad, the motor will stop regardless of signals on
Start
Auto-Start
and
.
A signal applied will put the adjustable frequency drive into auto mode
Auto On
as if the keypad button
[53]
Uses the input as an INCREASE signal to the Digital Potentiometer func-
tion described in parameter group 3-9*
Uses the input as a DECREASE signal to the Digital Potentiometer func-
tion described in parameter group 3-9*
Uses the input to CLEAR the Digital Potentiometer reference described
in parameter group 3-9*
(Terminal 29 or 33 only) Input for increment counting in the SLC counter.
(Terminal 29 or 33 only) Input for decrement counting in the SLC counter.
Input for reset of counter A.
Mains
Freeze Output
[20], which means that in
Start
Jog
[8],
Off
Auto-Start
and
. Press either the
Hand Start
Auto Start
and
active again. If no
Auto-Start
nor
, the motor will stop regardless
Auto-Start
. If pressing the
has been pressed. See also
TR200 Programming Guide
Failure. Line fail-
Fire Mode
.
Freeze out-
[14] or
Hand On
and
button on the
Hand On
Hand
Off
Hand
Hand Start