Trane TR150 Programming Manual
Hide thumbs Also See for TR150:

Advertisement

Quick Links

TR150 Programming Guide
BAS-SVP16A-EN
BAS-SVP16A-EN
September 2013

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TR150 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Trane TR150

  • Page 1 TR150 Programming Guide BAS-SVP16A-EN BAS-SVP16A-EN September 2013...
  • Page 2: Table Of Contents

    1.3 Safety Symbols 1.4 Safety Precautions 1.5 Additional Resources 1.6 Definitions 1.7 Electrical Overview 2 How to Program 2.1 Programming with Trane Drive Utility (TDU) 2.2 Keypad 2.3 Menus 2.3.1 Status Menu 2.3.2 Quick Menu 2.3.3 Start-up Wizard for Open Loop Applications 2.3.4 Main Menu...
  • Page 3 Contents TR150 Programming Guide 4.1 Alarms and Warnings 4.2 Alarm Words 4.3 Warning Words 4.4 Extended Status Words 4.5 List of Warnings and Alarms 5 Parameter Lists 5.1 Parameter Options 5.1.1 Default Settings 5.1.2 0-** Operation/Display 5.1.3 1-** Load and Motor 5.1.4 2-** Brakes...
  • Page 4: Introduction

    Introduction TR150 Programming Guide 1 Introduction 1.1 Purpose of the Manual 1.4 Safety Precautions This programming guide provides information for WARNING advanced programming of the frequency converter. It The voltage of the frequency converter is dangerous provides a complete overview of all parameters as well as whenever connected to mains.
  • Page 5 Introduction TR150 Programming Guide WARNING WARNING Safety Regulations Warning against unintended start The mains supply to the frequency converter The motor can be brought to a stop by means must be disconnected whenever repair work is of digital commands, bus commands, references to be carried out.
  • Page 6: Additional Resources

    Introduction TR150 Programming Guide WARNING Trane technical literature is available in print from your local Trane Sales Office or at: HIGH VOLTAGE www.trane.com/vfd Disconnect all electric power, including remote disconnects. Follow proper lockout/tagout procedures to 1.6 Definitions ensure the power cannot be inadvertently energized.
  • Page 7 Introduction TR150 Programming Guide Break-away torque Analog outputs The analog outputs can supply a signal of 0-20 mA, 4-20 mA, or a digital signal. Automatic Motor Adaptation, AMA AMA algorithm determines the electrical parameters for the connected motor at standstill.
  • Page 8 Introduction TR150 Programming Guide mechanism. Restart is prevented until the cause of the Residual Current Device. fault has disappeared and the trip state is cancelled by activating reset or, in some cases, by being programmed Set-up to reset automatically. Trip may not be used for personal Parameter settings in 2 set-ups can be saved.
  • Page 9: Electrical Overview

    Introduction TR150 Programming Guide 1.7 Electrical Overview Illustration 1.2 Basic Wiring Schematic Drawing NOTICE There is no access to UDC- and UDC+ on the following units: IP20 380-480 V 30-90 kW IP20 200-240 V 15-45 kW IP20 525-600 V 2.2-90 kW IP54 380-480 V 22-90 kW BAS-SVP16A-EN - Rev.
  • Page 10: How To Program

    The frequency converter can be programmed from a PC active and edit set-up differ, both numbers are shown in via RS-485 COM port by using the Trane Drive Utility the display (set-up 12). The number flashing, indicates the (TDU). This software can either be ordered using code edit set-up.
  • Page 11: Menus

    How to Program TR150 Programming Guide 2.3.3 Start-up Wizard for Open Loop Applications 2.3 Menus The built-in wizard menu guides the installer through the 2.3.1 Status Menu set up of the frequency converter to an open loop application. An open loop application is here an...
  • Page 12 How to Program TR150 Programming Guide Illustration 2.4 Open Loop Set-up Wizard BAS-SVP16A-EN - Rev. 2013-09-05...
  • Page 13 How to Program TR150 Programming Guide Start-up Wizard for Open Loop Applications Parameter Range Default Function 0-03 Regional Settings [0] International [1] US 0-06 GridType [0] 200-240 V/50 Hz/IT-grid Size related Select operating mode for restart upon [1] 200-240 V/50 Hz/Delta...
  • Page 14 How to Program TR150 Programming Guide Parameter Range Default Function 1-24 Motor Current 0.01-10000.00 A Size related Enter motor current from nameplate data 1-25 Motor Nominal 100.0-9999.0 RPM Size related Enter motor nominal speed from nameplate data Speed 1-26 Motor Cont. Rated 0.1-1000.0...
  • Page 15 How to Program TR150 Programming Guide Parameter Range Default Function 6-11 Terminal 53 High 0-10 V 10 V Enter the voltage that corresponds to the high Voltage reference value 6-12 Terminal 53 Low 0-20 mA Enter the current that corresponds to the low...
  • Page 16 How to Program TR150 Programming Guide Illustration 2.5 Closed Loop Set-up Wizard BAS-SVP16A-EN - Rev. 2013-09-05...
  • Page 17 How to Program TR150 Programming Guide Closed Loop Set-up Wizard Parameter Range Default Function 0-03 Regional Settings [0] International [1] US 0-06 GridType [0] -[[132] see start -up wizard Size selected Select operating mode for restart upon for open loop application...
  • Page 18 How to Program TR150 Programming Guide Parameter Range Default Function 1-73 Flying Start [0] Disabled Select [1] Enable to enable the frequency [1] Enabled converter to catch a spinning motor. I.e. fan applications. When PM is selected, Flying Start is enabled.
  • Page 19 How to Program TR150 Programming Guide Motor Set-up The Quick Menu Motor Set-up guides through the needed motor parameters. Parameter Range Default Function 0-03 Regional Settings [0] International [1] US 0-06 GridType [0] -[132] see start -up wizard for Size selected...
  • Page 20: Main Menu

    Once the set-up of a frequency converter is complete, setting's value from another different value, the parameter Trane recommends to store the data in the keypad or on a will NOT be listed in Changes Made. PC via Trane Drive Utility (TDU) tool.
  • Page 21 How to Program TR150 Programming Guide Reconnect the mains supply - the frequency converter is now reset. Except the following parameters: 8-30 Protocol 8-31 Address 8-32 Baud Rate 8-33 Parity / Stop Bits 8-35 Minimum Response Delay 8-36 Maximum Response Delay...
  • Page 22: Parameters

    Parameters TR150 Programming Guide 3 Parameters 0-04 Operating State at Power-up Option: Function: 3.1 Main Menu - Operation and Display - input as before the frequency converter was Group 0 powered down. Parameters related to the fundamental functions of the...
  • Page 23 Parameters TR150 Programming Guide 0-06 GridType 0-10 Active Set-up Option: Function: Option: Function: [131] 525-600V/60Hz/Delta Select the set-up in which the frequency converter is to operate. [132] 525-600V/60Hz Set-up 1 Set-up 1 is active. 0-07 Auto DC Braking Set-up 2 Set-up 2 is active.
  • Page 24 Parameters TR150 Programming Guide 0-30 Custom Readout Unit Option: Function: [30] kg/s [31] kg/min [32] kg/h [33] t/min [34] [40] [41] m/min [45] [60] Degree Celsius [70] mbar [71] [72] Illustration 3.1 Custom Readout [73] [74] m Wg [80] The relation depends on the type of unit selected in...
  • Page 25 Parameters TR150 Programming Guide 3.1.5 0-5* Copy/Save 0-37 Display Text 1 Range: Function: Copy parameter settings between set-ups and to/from the [0 - 0 ] In this parameter it is possible to write an individual keypad. text string to be read via serial communication.
  • Page 26: Main Menu - Load And Motor - Group

    Parameters TR150 Programming Guide 1-03 Torque Characteristics Option: Function: 3.2 Main Menu - Load and Motor - Group 1 Variable For speed control of centrifugal pumps and fans. Parameters related to the motor nameplate load compen- Torque Also to be used when controlling more than sations and application load type.
  • Page 27 Parameters TR150 Programming Guide 1-17 Voltage filter time const. 1-10 Motor Construction 1-20 Motor Power [kW] Select the motor construction type. Other parameters will be 1-22 Motor Voltage changed when changing motor type selection 1-23 Motor Frequency Option: Function: 1-24 Motor Current Asynchron For asynchronous motors.
  • Page 28 Parameters TR150 Programming Guide 1-16 High Speed Filter Time Const 1-20 Motor Power Range: Function: Range: Function: Size related [ 0.01 - High pass-filter damping time constant [23] 55 kW - 75 hp 20 s] determines the response time to load...
  • Page 29 Parameters TR150 Programming Guide NOTICE 1-29 Automatic Motor Adaption (AMA) Option: Function: If one of the settings in parameter group 1-2* Motor NOTICE Data is changed, the advanced motor parameters, 1-30 Stator Resistance (Rs) to 1-39 Motor Poles, will return This parameter cannot be adjusted to default setting.
  • Page 30 Parameters TR150 Programming Guide 1-39 Motor Poles 1-55 U/f Characteristic - U Range: Function: Range: Function: NOTICE [2 - Size related [0 - Enter voltage at each frequency point to 100 ] 999 V] manually form a U/f characteristic This parameter cannot be adjusted matching motor.
  • Page 31 Parameters TR150 Programming Guide 1-63 Slip Compensation Time Constant 1-73 Flying Start Range: Function: Option: Function: 0.1 s [ 0.05 - Enter the slip compensation reaction speed. A below 2.5%-5%, in the time set in 2-07 Parking Time. 5.00 s] high value results in slow reaction, and a low value results in quick reaction.
  • Page 32 1-90 Motor Thermal Protection Option: Function: Using , the motor temperature is calculated based on frequency, speed and time. Trane recommends using the function, if a thermistor is not present. The functionality is the same for asynchronous motors and PM motors.
  • Page 33: Main Menu - Brakes - Group

    Parameters TR150 Programming Guide 3.3 Main Menu - Brakes - Group 2 2-06 Parking Current Range: Function: 2-00 DC Hold/Motor Preheat Current 100 % [0 - Set current as percentage of rated motor Range: Function: 150 %] current, 1-24 Motor Current. Active in...
  • Page 34: Main Menu - Reference/Ramps - Group

    Parameters TR150 Programming Guide 3-10 Preset Reference Range: Function: 3.4 Main Menu - Reference/Ramps - Group [-100 - Enter up to 8 different preset references (0-7) in 100 %] this parameter, using array programming. Select 3.4.1 3-0* Reference Limits Preset Reference bit 0/1/2 [16] , [17] or [18] for...
  • Page 35 Parameters TR150 Programming Guide 3.4.3 3-4* Ramp 1 3-16 Reference 2 Source Option: Function: Configure the ramp parameter, ramping times, for each of Select the input to be used for the the 2 ramps (parameter group 3-4* Ramp 1 and parameter second reference signal.
  • Page 36 Parameters TR150 Programming Guide 3.4.4 3-5* Ramp 2 Selecting ramp parameters, see parameter group 3-4* Ramp 1. 3-51 Ramp 2 Ramp Up Time Range: Function: Size [0.05 Enter acceleration time from 0 Hz to related - 3600 1-23 Motor Frequency if Asynchronous motor is selected.
  • Page 37: Main Menu - Limits/Warnings - Group

    Parameters TR150 Programming Guide 3.5 Main Menu - Limits/Warnings - Group 4 4-18 Current Limit Range: Function: 3.5.1 4-1* Motor Limits 4-18 Current Limit is not automatically reset to the default setting. Define current and speed limits for the motor, and the...
  • Page 38 Parameters TR150 Programming Guide 4-51 Warning Current High 4-58 Missing Motor Phase Function Range: Function: Option: Function: NOTICE Size [ 0.0 - Enter the I value. When the motor HIGH related 194.0 A] current exceeds this limit, a bit in the This parameter cannot be adjusted while the statusword is set.
  • Page 39 Parameters TR150 Programming Guide NOTICE Smaller frequency converters have a ramp time of 3 seconds which can make it difficult to set the bypass speeds. Adjust the ramp times in 3-41 Ramp 1 Ramp Up Time and 3-42 Ramp 1 Ramp Down Time.
  • Page 40: Main Menu - Digital In/Out - Group

    Parameters TR150 Programming Guide 3.6 Main Menu - Digital In/Out - Group 5 Digital input Description function 3.6.1 5-0* Digital I/O Mode [5] DC-brake inverse Inverted input for DC braking (NC). Stops motor by energising it with DC current for...
  • Page 41 Parameters TR150 Programming Guide Digital input Description Digital input Description function function [19] Freeze reference Freeze actual reference. The frozen [52] Run permissive The input terminal, for which the Run reference is now the point of enable/ permissive has been programmed must condition for Speed up and Speed down be logic “1”...
  • Page 42 Parameters TR150 Programming Guide Digital input Description 5-10 Terminal 18 Digital Input function Parameter for configuring the input function on input terminal 18. Refer to Table 3.3 for setting options. [63] Counter B (up) Input for increment counting in the SLC...
  • Page 43 Parameters TR150 Programming Guide 5-12 Terminal 27 Digital Input 5-13 Terminal 29 Digital Input Parameter for configuring the input function on input terminal Parameter for configuring the input function on input terminal Option: Function: Option: Function: No operation [16] Preset ref bit 0...
  • Page 44 Parameters TR150 Programming Guide 5-40 Function Relay 5-40 Function Relay Array (Relay 1 [0], Relay 2 [1]) Array (Relay 1 [0], Relay 2 [1]) Select options to define the function of the relays. Select options to define the function of the relays.
  • Page 45 Parameters TR150 Programming Guide 5-40 Function Relay 5-40 Function Relay Array (Relay 1 [0], Relay 2 [1]) Array (Relay 1 [0], Relay 2 [1]) Select options to define the function of the relays. Select options to define the function of the relays.
  • Page 46 Parameters TR150 Programming Guide Illustration 3.9 Pulse Input Illustration 3.7 On Delay, Relay 5-50 Term. 29 Low Frequency Range: Function: 4 Hz [4 - 31999 Enter the low frequency limit corresponding 5-42 Off Delay, Relay to the low motor shaft speed (i.e. low Array[2]: Relay1[0], Relay2[1] reference value) in 5-52 Term.
  • Page 47 Parameters TR150 Programming Guide 5-53 Term. 29 High Ref./Feedb. Value Range: Function: [-4999 - 4999 ] Enter the high reference value Size [-999999.999 - [RPM] for the motor shaft related 999999.999 speed and the high feedback ReferenceFeed- value, see also 5-58 Term. 33 backUnit] High Ref./Feedb.
  • Page 48: Main Menu - Analog In/Out - Group

    Parameters TR150 Programming Guide 3.7.2 6-1* Analog Input 53 3.7 Main Menu - Analog In/Out - Group 6 Parameter group for setting up the analog I/O configu- Parameters for configuring the scaling and limits for ration and the digital output. The frequency converter is analog input 53 (terminal 53).
  • Page 49 Parameters TR150 Programming Guide 6-16 Terminal 53 Filter Time Constant 6-25 Terminal 54 High Ref./Feedb. Value Range: Function: Range: Function: but also increases the time delay through the Size related [-4999 - Enter the reference or feedback value filter. 4999 ]...
  • Page 50 Parameters TR150 Programming Guide 6-72 Terminal 45 Digital Output 6-72 Terminal 45 Digital Output Option: Function: Option: Function: Select the function of [82] SL digital output C Terminal 45 as a [83] SL digital output D digital current output. [160] No alarm...
  • Page 51 Parameters TR150 Programming Guide 3.7.5 6-9* Analog/Digital Output 42 6-92 Terminal 42 Digital Output Option: Function: Parameters for configuring the limits for analog/digital [17] Above speed, high output Terminal 42. Analog outputs are current outputs: [19] Below feedback, low 0/4-20 mA. Resolution on analog outputs is 12 bit. Analog...
  • Page 52 Parameters TR150 Programming Guide 6-94 Terminal 42 Output Max Scale Range: Function: [0 - Scale for the maximum output (20 mA) of the scaling at Terminal 42. Set the value to be the percentage of the full range of the variable selected in 6-91 Terminal 42 Analog Output.
  • Page 53: Main Menu - Communications And Options - Group

    Parameters TR150 Programming Guide 3.8.2 8-3* Drive 3.8 Main Menu - Communications and Options - Group 8 8-30 Protocol 3.8.1 8-0* General Settings Option: Function: Select the protocol for the integrated RS-485 8-01 Control Site port. Option: Function: Communication according to the Drive Select [0] Digital and ctrl.word for using...
  • Page 54 Parameters TR150 Programming Guide 8-33 Parity / Stop Bits 8-51 Quick Stop Select Option: Function: Option: Function: [1] Odd Parity, 1 Stop Select control of the Quick Stop function via the terminals (digital input) and/or via the bus. [2] No Parity, 1 Stop Bit...
  • Page 55 Parameters TR150 Programming Guide 8-53 Start Select 8-56 Preset Reference Select Option: Function: Option: Function: Logic Activates Start command via the serial Select control of the frequency converter Preset communication port, AND additionally via one of Reference selection via the terminals (digital the digital inputs.
  • Page 56 Parameters TR150 Programming Guide 3.8.5 8-8* FC Port Diagnostics These parameters are used for monitoring the Bus communication via the Drive Port. 8-80 Bus Message Count Range: Function: [0 - 65536 ] This parameter shows the number of valid telegrams detected on the bus.
  • Page 57: Main Menu - Smart Logic - Group

    Parameters TR150 Programming Guide 3.9 Main Menu - Smart Logic - Group 13 13-00 SL Controller Mode Option: Function: 3.9.1 13-** Prog. Features Select [1] On to enable the Smart Logic Control to start when a start command is present, e.g. via a Smart Logic Control (SLC) is a sequence of user defined digital input.
  • Page 58 Parameters TR150 Programming Guide 13-01 Start Event 13-02 Stop Event Option: Function: Option: Function: [27] Logic rule 1 Use the result of logic rule 1 in the In range See 13-01 Start Event for further logic rule. description. [28] Logic rule 2...
  • Page 59 Parameters TR150 Programming Guide 3.9.3 13-1* Comparators 13-02 Stop Event Option: Function: Comparators are used for comparing continuous variables [34] Digital input DI19 (i.e. output frequency, output current, analog input etc.) to [35] Digital input DI27 Use the value of DI27 in the logic rule fixed preset values.
  • Page 60 Parameters TR150 Programming Guide 13-11 Comparator Operator Array [6] Option: Function: Approx.Equal Select [1] ≈ for the result of the evaluation to be TRUE, when the variable selected in 13-10 Comparator Operand is approxi- mately equal to the fixed value in 13-12 Comparator Value.
  • Page 61 Parameters TR150 Programming Guide 13-40 Logic Rule Boolean 1 13-40 Logic Rule Boolean 1 Array [6] Array [6] Option: Function: Option: Function: [23] Comparator 1 Use the result of comparator 1 in the [61] Logic rule 5 Use the result of logic rule 5 in the logic rule.
  • Page 62 Parameters TR150 Programming Guide 13-42 Logic Rule Boolean 2 13-43 Logic Rule Operator 2 Array [6] Array [6] Option: Function: Option: Function: [19] Warning Disabled [20] Alarm (trip) [21] Alarm (trip lock) [22] Comparator 0 AND NOT [23] Comparator 1...
  • Page 63 Parameters TR150 Programming Guide 13-44 Logic Rule Boolean 3 13-51 SL Controller Event Array [6] Array [20] Option: Function: Option: Function: [42] Auto Reset Trip [35] Digital input DI27 [50] Comparator 4 [36] Digital input DI29 [51] Comparator 5 [39] Start command...
  • Page 64 Parameters TR150 Programming Guide 13-52 SL Controller Action 13-52 SL Controller Action Array [20] Array [20] Option: Function: Option: Function: [18] Select ramp 1 Selects ramp 1 [71] Start Timer 4 Starts timer 4, see 13-20 SL Controller Timer for further description.
  • Page 65: Main Menu - Special Functions - Group

    Parameters TR150 Programming Guide 3.10 Main Menu - Special Functions - Group 14-08 Damping Gain Factor Range: Function: 96 % [0 - 100 %] Damping factor for DC-Link Voltage 3.10.1 14-0* Inverter Switching Compensation. 14-01 Switching Frequency 3.10.2 14-1* Mains On/Off...
  • Page 66 Parameters TR150 Programming Guide 14-20 Reset Mode 14-23 Typecode Setting Option: Function: Range: Function: Automatic reset x 7 [0 - 255 ] Typecode re-writing. Use this parameter to set the typecode matching the specific frequency Automatic reset x 8 converter.
  • Page 67 Parameters TR150 Programming Guide 3.10.5 14-5* Environment 14-63 Min Switch Frequency Set the minimum switch frequency allowed by the output filter. These parameters help the frequency converter to operate Option: Function: under special environmental conditions. 8.0 kHz 14-50 RFI Filter 10.0 kHz...
  • Page 68: Main Menu - Drive Information - Group

    Parameters TR150 Programming Guide 3.11 Main Menu - Drive Information - Group 15-06 Reset kWh Counter Option: Function: Reset counter Select [1] Reset and press [OK] to reset the Parameter group containing frequency converter kWh counter to zero (see 15-02 kWh information such as operating data, hardware configu- Counter).
  • Page 69 Parameters TR150 Programming Guide 15-43 Software Version Range: Function: [0 - 0 ] View the software version of the frequency converter. 15-44 Ordered TypeCode Range: Function: [0 - 0 ] View the type code string used for re-ordering the frequency converter in its original configuration.
  • Page 70: Main Menu - Data Readouts - Group

    Parameters TR150 Programming Guide 3.12 Main Menu - Data Readouts - Group 16 16-03 Status Word Range: Function: [0 - 65535 ] View the Status word sent from the frequency 3.12.1 16-0* General Status converter via the serial communication port in hex code.
  • Page 71 Parameters TR150 Programming Guide 16-11 Power [hp] 16-36 Inv. Nom. Current Range: Function: Range: Function: 0 hp [0 - 1000 View the DC link power in hp. The value [0 - 655.35 View the inverter nominal current, which shown is calculated on the basis of the should match the nameplate data on the actual motor voltage and motor current.
  • Page 72 Parameters TR150 Programming Guide 16-61 Terminal 53 Setting 16-71 Relay Output [bin] Option: Function: Range: Function: View the setting of input terminal 53. [0 - View the setting of the relay. Current = 0; Voltage = 1. 65535 ] Bits definition:...
  • Page 73 Parameters TR150 Programming Guide 16-91 Alarm Word 2 Range: Function: [0 - 0xFFFFFFFFUL ] View the alarm word 2 sent via the serial communication port in hex code. 16-92 Warning Word Range: Function: [0 - 0xFFFFFFFFUL ] View the warning word sent via the serial communication port in hex code.
  • Page 74: Main Menu - Data Readouts 2 - Group

    Parameters TR150 Programming Guide 3.14.2 20-8* PI Basic Settings 3.13 Main Menu - Data Readouts 2 - Group Parameters for configuring the Process PI control. Parameters in this group are array parameters, where up to 20-81 PI Normal/ Inverse Control 10 fault logs can be viewed.
  • Page 75 Parameters TR150 Programming Guide 20-94 PI Integral Time Range: Function: 20 s [0.10 - Enter the process controller integral time. 9999 s] Obtain quick control through a short integral time, though if the integral time is too short, the process becomes unstable. An excessively long integral time disables the integral action.
  • Page 76: Main Menu - Application Functions - Group

    Parameters TR150 Programming Guide 3.15 Main Menu - Application Functions - The frequency converter activates 1-80 Function at Stop. The frequency converter is now in Sleep Group 22 mode. 3.15.1 22-4* Sleep Mode When error between Reference and Feedback is greater than 22-44 Wake-Up Ref./FB Diff, and the...
  • Page 77 Parameters TR150 Programming Guide NOTICE 22-45 Setpoint Boost Range: Function: Do not set 14-20 Reset Mode, to [13] Infinite auto reset, when 22-60 Broken Belt Function is set to [2] Trip. Doing control, it is advantageous to increase so causes the frequency converter to continuously cycle...
  • Page 78: Main Menu - Application Functions 2 - Group

    All other alarms occurring while Fire Mode activated are programmed for Fire Mode. In no event shall Trane be logged as usual. liable to the end user or any other party for any direct or...
  • Page 79 Parameters TR150 Programming Guide 3.16.2 24-1* Drive Bypass 24-05 FM Preset Reference Range: Function: The frequency converter includes a feature, which can be [-100 - 100 Enter the required preset reference/set point used to automatically activate an external electro- as a percentage of the Fire Mode Max mechanical bypass in case of the event of a Fire Mode Reference set in Hz.
  • Page 80 Parameters TR150 Programming Guide 24-11 Drive Bypass Delay Time Range: Function: [0 - Programmable in 1 s increments. Once the Bypass Function is activated in accordance with the setting in 24-10 Drive Bypass Function, the Bypass Delay Timer begins to operate. If the frequency converter...
  • Page 81: Troubleshooting

    Troubleshooting TR150 Programming Guide 4 Troubleshooting If an alarm cannot be reset, the reason may be that its cause has not been rectified, or the alarm is trip-locked, 4.1 Alarms and Warnings see Table 4.1. A warning or an alarm is signalled by the relevant LED on...
  • Page 82 Troubleshooting TR150 Programming Guide Description Warning Alarm/Trip Alarm/Trip Parameter Reference Lock Brake resistor power limit 2-13 Brake chopper short-circuited Brake check 2-15 Drive over temperature Motor phase U missing 4-58 Motor phase V missing 4-58 Motor phase W missing 4-58...
  • Page 83 Troubleshooting TR150 Programming Guide Description Warning Alarm/Trip Alarm/Trip Parameter Reference Lock Analog input 54 wrong settings NoFlow 22-2* Dry Pump 22-2* End of Curve 22-5* Broken Belt 22-6* Start Delayed 22-7* Stop Delayed 22-7* Clock Fault 0-7* Fire M was Active...
  • Page 84: Alarm Words

    Troubleshooting TR150 Programming Guide 4.2 Alarm Words 4.3 Warning Words 16-90 Alarm 16-91 Alarm Word Word 2 16-92 Warning 16-93 Warning Word Word 2 Pwr.Card Temp ServiceTrip, Pwr.Card Temp Earth Fault Typecode Earth Fault Sparepart Ctrl. Word TO Ctrl. Word TO...
  • Page 85: Extended Status Words

    Troubleshooting TR150 Programming Guide 4.4 Extended Status Words 4.5 List of Warnings and Alarms WARNING 16-94 Ext. 16-95 Ext. Status Status Word Word 2 Hazardous Service Procedures! Ramping The maintenance and troubleshooting procedures AMA running Hand/Auto recommended in this section of the manual could result...
  • Page 86 Troubleshooting TR150 Programming Guide WARNING/ALARM 9, Inverter overloaded CAUTION The frequency converter is about to cut out because of an Disconnect power before proceeding. overload (too high current for too long). The counter for electronic, thermal inverter protection gives a warning at Troubleshooting: 90% and trips at 100%, while giving an alarm.
  • Page 87 ALARM 38, Internal fault nameplate and the part numbers of the cards to check It may be necessary to contact your Trane supplier. compatibility. ALARM 44, Earth fault II...
  • Page 88 Parameter Lists TR150 Programming Guide 5 Parameter Lists 5.1 Parameter Options 5.1.1 Default Settings Changes during operation ”TRUE” means that the parameter can be changed while the frequency converter is in operation and “FALSE” means that the frequency converter must be stopped before a change can be made.
  • Page 89: Operation/Display

    Parameter Lists TR150 Programming Guide 5.1.2 0-** Operation/Display Par. No. # Parameter description Default value 2-set-up Change Conver- Type during sion index operation 0-0* Basic Settings 0-01 Language [0] English 1 set-up TRUE Uint8 0-03 Regional Settings ExpressionLimit 1 set-up...
  • Page 90 Parameter Lists TR150 Programming Guide Par. No. # Parameter description Default value 2-set-up Change Conver- Type during sion index operation 1-26 Motor Cont. Rated Torque ExpressionLimit All set-ups FALSE Uint32 1-29 Automatic Motor Adaption (AMA) [0] Off 1 set-up FALSE Uint8 1-3* Adv.
  • Page 91: Brakes

    Parameter Lists TR150 Programming Guide 5.1.4 2-** Brakes Par. No. # Parameter description Default value 2-set-up Change Conver- Type during sion index operation 2-0* DC-Brake 2-00 DC Hold/Motor Preheat Current 50 % All set-ups TRUE Uint16 2-01 DC Brake Current...
  • Page 92: Digital In/Out

    Parameter Lists TR150 Programming Guide Par. No. # Parameter description Default value 2-set-up Change Conver- Type during sion operation index 4-40 Warning Freq. Low ExpressionLimit All set-ups TRUE uint16 4-41 Warning Freq. High ExpressionLimit All set-ups TRUE uint16 4-5* Adj. Warnings...
  • Page 93: Analog In/Out

    Parameter Lists TR150 Programming Guide 5.1.8 6-** Analog In/Out Par. No. # Parameter description Default value 2-set-up Change Conver- Type during sion index operation 6-0* Analog I/O Mode 6-00 Live Zero Timeout Time 10 s All set-ups TRUE Uint8 6-01...
  • Page 94: Comm. And Options

    Parameter Lists TR150 Programming Guide 5.1.9 8-** Comm. and Options Par. No. # Parameter description Default value 2-set-up Change Conver- Type during sion operation index 8-0* General Settings 8-01 Control Site [0] Digital and ctrl.word All set-ups TRUE Uint8 8-02...
  • Page 95: Special Functions

    Parameter Lists TR150 Programming Guide Par. No. # Parameter description Default value 2-set-up Change Conver- Type during sion operation index 13-03 Reset SLC [0] Do not reset SLC 1 set-up TRUE Uint8 13-1* Comparators 13-10 Comparator Operand [0] Disabled 1 set-up...
  • Page 96: Drive Information

    Parameter Lists TR150 Programming Guide 5.1.12 15-** Drive Information Par. No. # Parameter description Default value 2-set-up Change Conver- Type during sion index operation 15-0* Operating Data 15-00 Operating Hours All set-ups TRUE Uint32 15-01 Running Hours All set-ups TRUE...
  • Page 97: Info & Readouts

    Parameter Lists TR150 Programming Guide 16-36 Inv. Nom. Current 1 set-up TRUE Uint16 16-37 Inv. Max. Current 1 set-up TRUE Uint16 16-38 SL Controller State 0 N/A 1 set-up TRUE Uint8 16-5* Ref. & Feedb. 16-50 External Reference 1 set-up...
  • Page 98: Drive Closed Loop

    Parameter Lists TR150 Programming Guide 5.1.15 20-** Drive Closed Loop Par. No. # Parameter description Default value 2-set-up Change Conver- Type during sion index operation 20-0* Feedback 20-00 Feedback 1 Source [0] No function All set-ups TRUE Uint8 20-01 Feedback 1 Conversion...
  • Page 99: Index

    Index TR150 Programming Guide Comparator Index Operand....................58 Operator....................58 Value..................... 59 Action At Inverter Fault..............65 Comparators..................58 Active Set-up..................22 Control Site......................52 Address....................52 Timeout Time..................52 Advanced Vector Control..............5 Word..................... 69 AEO......................65 Counter A......................71 Alarm B......................
  • Page 100 Index TR150 Programming Guide Keypad Control....................66 Keypad....................6, 9 Monitor....................66 Copy....................0 Fault Messages..................84 KWh Counter..................67 Port Diagnostics................55 Port Settings..................52 Language....................21 Feedback Latched Start..................39 Feedback..................... 73 1 Conversion..................73 1 Source....................73 LCP......................
  • Page 101 Poles...................... 29 Relative Reference................33 Set-up....................10 Programming Speed Direction................36 Set-up....................22 Speed High Limit................36 With Trane Drive Utility (TDU)............9 Speed Low Limit................36 Protection Mode..................5 Status....................69 Therma Protection................31 Protocol....................52 Thermal....................70 Pulse Input, 5-5*.................. 45 Voltage..................
  • Page 102 Index TR150 Programming Guide Serial Communication................43 Communication Port................. 5 Terminal Setpoint Boost..................76 18 Digital Input................. 41 19 Digital Input................. 41 Set-up Copy................... 24 27 Digital Input................. 42 29 Digital Input................. 42 Controller Action................62 42 Analog Output................50 Controller Mode................
  • Page 103 Date September 2013 Supersedes www.trane.com Trane has a policy of continous product and product data improvement and reserves the right to For more information, contact your local Trane change design and specifications without notice. office or e-mail us at comfort@trane.com Rev.

Table of Contents