How to Program
Initialization to Default Settings
Initialize the adjustable frequency drive to default settings in two ways:
Recommended initialization (via par.14-22
1.
Select par.14-22
Operation Mode
2.
Press [OK]
3.
Select "Initialization"
4.
Press [OK]
5.
Cut off the line power supply and wait until the display turns off.
6.
Reconnect the line power supply - the adjustable frequency drive is now reset.
7.
Change par.14-22
Operation Mode
NOTE
Resets parameters selected in Personal Menu with default factory setting.
par.14-22
Operation Mode
initializes all except:
par.14-50
RFI 1
par.8-30
Protocol
par.8-31
Address
par.8-32
Baud Rate
par.8-35
Minimum Response Delay
par.8-36
Maximum Response Delay
par.8-37
Maximum Inter-Char Delay
par.15-00
Operating Hours
to par.15-05
par.15-20
Historic Log: Event
to par.15-22
par.15-30
Alarm Log: Error Code
Manual initialization
1.
Disconnect from the line power and wait until the display turns off.
2a.
Press [Status] - [Main Menu] - [OK] at the same time while powering up for LCP 102, Graphical Display
2b.
Press [Menu] while powering up for LCP 101, Numerical Display
3.
Release the keys after 5 s.
4.
The adjustable frequency drive is now programmed according to default settings.
This procedure initializes all except: par.15-00
NOTE
When you carry out manual initialization, you also reset serial communication, par.14-50
Removes parameters selected in par.25-00
NOTE
After initialization and power cycling, the display will not show any information until after a couple of minutes.
3-18
Operation
Normal Operation
back to
Over Volts
Historic Log: Time
to par.15-32
Alarm Log: Time
Operating
Hours; par.15-03 Power-ups; par.15-04
Cascade
Controller.
Mode)
.
Over
Temps; par.15-05
RFI 1
TR200 Programming Guide
Over
Volts.
and fault log settings.