Parameter Description
[4]
Max. speed
[5]
Stop and trip
6-02 Fire Mode Live Zero Timeout Function
Option:
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
6-1* Analog Input 1
Parameters for configuring the scaling and limits for analog input 1 (terminal 53).
6-10 Terminal 53 Low Voltage
Range:
0.07 V* [Application dependant]
6-11 Terminal 53 High Voltage
Range:
10.00 V* [Application dependant]
6-12 Terminal 53 Low Current
Range:
4.00
[Application dependant]
mA*
4-84
Function:
The function set in par.6-01
if the input signal on analog inputs is below 50% of the value defined in
parameter group 6-1* to 6-6* "Terminal xx Low Current" or "Terminal
xx Low Voltage" for a time period defined in par.6-00
Time.
Function:
Enter the low voltage value. This analog input scaling value should cor-
respond to the low reference/feedback value set in par.6-14
Low Ref./Feedb.
Value.
Function:
Enter the high voltage value. This analog input scaling value should cor-
respond to the high reference/feedback value set in par.6-15
High Ref./Feedb.
Value.
Function:
Enter the low current value. This reference signal should correspond to
the low reference/feedback value, set in par.6-14
Feedb.
Value. The value must be set at >2 mA in order to activate the Live
Zero Timeout Function in par.6-01
Live Zero Timeout Function
Live Zero Timeout
Terminal 53 Low Ref./
Live Zero Timeout
Function.
TR200 Programming Guide
will be activated
Terminal 53
Terminal 53