14-31 Current Lim Contr, Integration Time
Range:
0.020 s* [0.002 - 2.000 s]
14-32 Current Lim Ctrl, Filter Time
Range:
26.0
[1.0 - 100.0 ms]
ms*
14-4*Energy Optimization
Parameters for adjusting the energy optimization level in both Variable Torque (VT) and Automatic Energy Op-
timization (AEO) mode.
Automatic Energy Optimization is only active if par.1-03
Optim. Compressor
Auto Energy Optim. VT
[2] or
14-40 VT Level
Range:
66 %*
[40 - 90 %]
14-41 AEO Minimum Magnetization
Range:
Applica-
[40 - 75 %]
tion de-
pend-
ent*
14-42 Minimum AEO Frequency
Range:
10 Hz*
[5 - 40 Hz]
14-43 Motor Cos-Phi
Range:
Applica-
[0.40 - 0.95 N/A]
tion de-
pend-
ent*
TR200 Programming Guide
Function:
Controls the current limit control integration time. Setting it to a lower
value makes it react faster. A setting too low leads to control instability.
Function:
Torque
Characteristics, is set for either
[3].
Function:
Enter the level of motor magnetization at low speed. Selection of a low
value reduces energy loss in the motor, but also reduces load capability.
This parameter cannot be adjusted while the motor is running.
Function:
Enter the minimum allowable magnetization for AEO. Selection of a low
value reduces energy loss in the motor, but can also reduce resistance
to sudden load changes.
Function:
Enter the minimum frequency at which the Automatic Energy Optimiza-
tion (AEO) is to be active.
Function:
The cos(phi) setpoint is automatically set for optimum AEO performance
during AMA. This parameter should normally not be altered. However,
in some situations it may be necessary to enter a new value to fine tune.
Parameter Description
Auto Energy