Parameter Description
4-150
Bit 14: Maintenance Text 1
Bit 15: Maintenance Text 2
Bit 16: Maintenance Text 3
Bit 17: Maintenance Text 4
Valve
Position 4
Position 3
Pump seals
Drive sys-
Position 2
tem health
check
Position 1
0 hex
-
1 hex
-
2 hex
-
3 hex
-
4 hex
-
5 hex
-
6 hex
-
7 hex
-
8 hex
+
9 hex
+
A hex
+
B hex
+
C hex
+
D hex
+
E hex
+
F hex
+
Example:
The Preventive Maintenance Word shows 040Ahex.
Position
1
hex value
0
The first digit 0 indicates that no items from the fourth row requires
maintenance
The second digit 4 refers to the third row indicating that the drive cooling
fan requires maintenance
The third digit 0 indicates that no items from the second row requires
maintenance
The fourth digit A refers to the top row indicating that the valve and the
pump bearings require maintenance
Fan bear-
Pump bear-
ings
ings
Tempera-
Flow trans-
ture trans-
mitter
mitter
Drive cool-
Filter
ing fan
-
-
-
-
-
+
-
+
+
-
+
-
+
+
+
+
-
-
-
-
-
+
-
+
+
-
+
-
+
+
+
+
2
3
4
0
TR200 Programming Guide
Motor bear-
ings
Pressure
transmitter
Fan belt
Warranty
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
4
A