Trane TR200 Programming Manual page 200

Hide thumbs Also See for TR200:
Table of Contents

Advertisement

20-3* Feedback Adv. Conversion
In air conditioning compressor applications it is often useful to control the system based on the temperature of
the refrigerant. However, it is generally more convenient to directly measure its pressure. This parameter group
allows the adjustable frequency drive's PID controller to convert refrigerant pressure measurements into tem-
perature values.
20-30 Refrigerant
Option:
[0] *
R22
[1]
R134a
[2]
R404a
[3]
R407c
[4]
R410a
[5]
R502
[6]
R744
[7]
User-defined
20-31 User-defined Refrigerant A1
Range:
10.0000
[8.0000 - 12.0000 N/A]
N/A*
20-32 User-defined Refrigerant A2
Range:
-2250.00
[-3000.00 - -1500.00 N/A]
N/A*
20-33 User-defined Refrigerant A3
Range:
250.000
[200.000 - 300.000 N/A]
N/A*
TR200 Programming Guide
Function:
Select the refrigerant used in the compressor application. This parameter
must be specified correctly for the pressure to temperature conversion
to be accurate. If the refrigerant used is not listed in choices [0] through
User defined
[6], select
[7], use par.20-31
par.20-32
User-defined Refrigerant A2
frigerant A3
to provide A1, A2 and A3 for the equation below:
A
Temperature
=
(
(
+ 1 )
ln
Pe
Function:
Use this parameter to enter the value of coefficient A1 when par.
User-defined
20-30
Refrigerant
is set to
Function:
Use this parameter to enter the value of coefficient A2 when par.
User-defined
20-30
Refrigerant
is set to
Function:
Use this parameter to enter the value of coefficient A3 when par.
User-defined
20-30
Refrigerant
is set to
Parameter Description
User-defined Refrigerant
and par.20-33
User-defined Re-
2
A
3
1 )
A
[7].
[7].
[7].
A1,
4-163