Parameter Description
24-11 Drive Bypass Delay Time
Range:
0 s*
[0 - 600 s]
4-214
Function:
Programmable in 1 s increments. Once the bypass function is activated
in accordance with the setting in par.24-10
bypass delay timer begins to operate. If the adjustable frequency drive
has been set for a number of restart attempts, the timer will continue to
run while the adjustable frequency drive tries to restart. If the motor re-
starts within the time period of the bypass delay timer, then the timer is
reset.
If the motor fails to restart at the end of the bypass delay time, the drive
bypass relay will be activated, which will have been programmed for
Bypass in par.5-40
Function
grammed in par.5-41
On Delay,
Relay, [Relay], then this time must also elapse before the relay action is
performed.
Where no restart attempts are programmed, the timer will run for the
delay period set in this parameter and will then activate the drive bypass
relay, which will have been programmed for Bypass in par.5-40
Relay, Function Relay. If a relay delay has also been programmed in par.
5-41
On Delay,
Relay, On Delay, Relay or par.5-42
lay], then this time must also elapse before the relay action is performed.
Drive Bypass
Relay. If a [Relay Delay] has also been pro-
Relay, [Relay] or par.5-42
Off Delay,
TR200 Programming Guide
Function, the
Off Delay,
Function
Relay, [Re-