22-60 Broken Belt Function
Selects the action to be performed if the broken belt condition is detected.
Option:
[0] *
OFF
[1]
Warning
[2]
Trip
NOTE
Do not set par.14-20
Reset Mode
so will cause the drive to continuously cycle between running and stopping when a broken belt condition is detected.
NOTE
If the drive is equipped with a constant speed bypass with an automatic bypass function that starts the bypass if the
drive experiences a persistent alarm condition, be sure to disable the bypass' automatic bypass function, if [2] Trip is
selected as the broken belt function.
22-61 Broken Belt Torque
Range:
10 %*
[0 - 100 %]
22-62 Broken Belt Delay
Range:
10 s
[0 - 600 s]
22-7* Short Cycle Protection
When controlling refrigeration compressors, often there will be a need for limiting the numbers of starts. One
way to do this is to ensure a minimum run time (time between a start and a stop) and a minimum interval
between starts.
This means that any normal stop command can be overridden by the
22-77
Minimum Run
Time) and any normal start command (Start/Jog/Freeze) can be overridden by the
Between Starts
function (par.22-76
None of the two functions are active if
Hand On
Off
or
, the two timers will be reset to 0, and not start counting until
command applied.
22-75 Short Cycle Protection
Option:
[0] *
Disabled
[1]
Enabled
TR200 Programming Guide
Function:
The drive will continue to run, but activate a Broken Belt Warning [W95].
A drive digital output or a serial communication bus can communicate a
warning to other equipment.
The drive will stop running and activate a Broken Belt alarm [A 95]. A
drive digital output or a serial communication bus can communicate an
alarm to other equipment.
to [13] Infinite auto reset when par.22-60
Function:
Sets the broken belt torque as a percentage of the rated motor torque.
Function:
Sets the time for which the broken belt conditions must be active before
carrying out the action selected in par.22-60
Interval between
Starts).
Hand On
Off
or
modes have been activated via the keypad. If selecting
Function:
Timer set in par.22-76
Timer set in par.22-76
Parameter Description
Broken Belt Function
Broken Belt
Minimum Run Time
Auto
is pressed and an active start
Interval between Starts
is disabled.
Interval between Starts
is enabled.
is set to [2] Trip. Doing
Function.
function (par.
Interval
4-191