Trane TR200 Programming Manual page 205

Hide thumbs Also See for TR200:
Table of Contents

Advertisement

Parameter Description
20-9* PID Controller
This group provides the ability to manually adjust this PID controller. By adjusting the PID controller parameters
the control performance may be improved. See section PID in the TR200 Design Guide,
lines on adjusting the PID controller parameters.
20-91 PID Anti Windup
Option:
[0]
Off
[1] *
On
20-93 PID Proportional Gain
Range:
0.50 N/
[0.00 - 10.00 N/A]
A*
If (Error x Gain) jumps with a value equal to what is set in par.20-14
troller will try to change the output speed equal to what is set in par.4-13
4-14
Motor Speed High Limit [Hz]
The proportional band (error causing output to change from 0–100%) can be calculated by means of the formula:
(
)
1
× (
Max Reference
Proportional Gain
NOTE: Always set the desired for par.20-14
controller in par. group 20-9*.
20-94 PID Integral Time
Range:
20.00 s* [0.01 - 10000.00 s]
4-168
Function:
Off
[0] The integrator will continue to change value also after output has
reached one of the extremes. This can afterwards cause a delay of
change of the output of the controller.
On
[1] The integrator will be locked if the output of the built-in PID con-
troller has reached one of the extremes (min or max value) and therefore
not able to add further change to the value of the process parameter
controlled. This allows the controller to respond more quickly when it
again can control the system.
Function:
but in practice of course limited by this setting.
)
Maximum Reference/Feedb.
Function:
Over time, the integrator accumulates a contribution to the output from
the PID controller as long as there is a deviation between the reference/
setpoint and feedback signals. The contribution is proportional to the size
of the deviation. This ensures that the deviation (error) approaches zero.
Quick response on any deviation is obtained when the integral time is
set to a low value. Setting it too low, however, may cause the control to
become unstable.
The value set is the time needed for the integrator to add the same con-
tribution as the proportional part for a certain deviation.
If the value is set to 10,000, the controller will act as a pure proportional
controller with a P-band based on the value set in par.20-93
tional
Gain. When no deviation is present, the output from the propor-
tional controller will be 0.
MG.11.Bx.yy
Maximum
Reference/Feedb., the PID con-
Motor Speed High Limit
before setting the values for the PID
TR200 Programming Guide
for guide-
[RPM]/par.
PID Propor-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents