This manual is intended to provide detailed information for the installation and operation of the option panel used in conjunction with a Trane variable frequency drive (VFD or drive). To enable efficient handling of the equipment, requirements are provided for installation of mechanical, electrical, and control wiring, proper grounding, and environmental considerations.
Display data indicates when in bypass. The circuitry may be supplied with either an input dis- connect switch or an input circuit breaker. Contactor Drive Mode Bypass Mode Test Mode Closed Open Open Closed Closed Open Open Open Open Open Closed Closed Table 1.2 Illustration 1.1: Basic 3-contactor Bypass Functions TR200 Option Panel Operating Instructions...
The EMB is available in three platforms: EMB(0), EMB1, and EMB2. The features available as options with each platform are listed in the following table. The ECB, also listed below, has all option features available. See Chapter 5 for additional details on the EMB and Chapter 6 for the ECB. TR200 Option Panel Operating Instructions...
When in the ON position, a trip fault removes power from the drive/bypass circuit and the switch moves to the TRIP setting. It must be moved to the RESET position momentarily after the fault has been cleared to reset the circuit breaker. TR200 Option Panel Operating Instructions...
Twoposition (ON/OFF) rotary switch disconnects main AC line input power to the drive only. Bypass selector switch The bypass selector switch is used for either the 2- contactor or 3-contactor bypass for EMB units. Illustration 1.3: Disconnects Bypass selector switch Main disconnect Drive disconnect TR200 Option Panel Operating Instructions...
If you give the transportation company a clear receipt for equipment that has been damaged or lost in transit, you do so at your own risk and expense. Trane IS WILLING TO ASSIST YOU TO COLLECT CLAIMS FOR LOSS OR DAMAGE, BUT WILLINGNESS ON OUR PART DOES NOT MAKE US RESPONSIBLE FOR COLLECTION OF CLAIMS OR REPLACEMENT OF MATERIAL.
A non-ventilated cabinet fitted with an air conditioner as a heat exchanger may be used. Conformal coated circuit boards may be specified to reduce the corrosive effects of a harsh environment. TR200 Option Panel Operating Instructions...
When applicable, use the specified fuse or an equivalent replacement only for internal option panel fuses. Fuse options include the drive disconnect and contactor fuses. See the nameplate label (table below) on the inside cover of the unit for option panel fuse ratings. TR200 Option Panel Operating Instructions...
Lift unit slightly using lifting rings with weight distributed evenly. • Remove skid and other supports from under drive. • For floor mounting applications, a floor mounting kit is available from Trane specifically designed to anchor drive to floor. Forklift •...
No additional back plate is required for drives with the option panel. • Units may be mounted flush to the wall or free standing. A free-standing mounting kit is available from Trane. • See table below for temperature ratings. TR200 Option Panel Operating Instructions...
Page 16
45° C 40° C C2, D1-D2 40° C 40° C Table 3.4 Illustration 3.3: Side Cooling Clearance, A-2 and A-3 Frames CEILING AIRFLOW 4.0 in min. 4.0 in min. AIRFLOW FLOOR Illustration 3.4: Cooling Airflow TR200 Option Panel Operating Instructions...
Power from the option enclosure to the motor (and earth ground) • Control wiring Control wiring should always be isolated from the high voltage power wiring. Avoid getting metal chips into electronics. Follow the connection procedures as illustrated in the drawing provided with the unit. TR200 Option Panel Operating Instructions...
The below figure represents a typical layout drawing. The following table provides definitions for drawing reference designators. (Not all reference designators are shown.) Illustration 3.6: Sample Mechanical Layout Diagram TR200 Option Panel Operating Instructions...
Removable access covers are provided for cable connections (see figure ). Re- move access covers prior to drilling holes to prevent metal shavings from damaging internal electronic components. • For some units, access holes are provided for input power, motor leads, and control wiring. TR200 Option Panel Operating Instructions...
Terminal Tightening Torques • Tighten all connections to the torque specifications provided. • The torque tightening specifications are located on the tightening torque and wire rating label inside the cover of the option panel (see figure below.) TR200 Option Panel Operating Instructions...
Motor wiring should always be as short as practical. Grounding (Earthing) WARNING GROUNDING HAZARD! FOR OPERATOR SAFETY, IT IS IMPORTANT TO GROUND OPTION PANEL PROPERLY. FAILURE TO GROUND OPTION PANEL PROPERLY COULD RESULT IN DEATH OR SERIOUS INJURY. TR200 Option Panel Operating Instructions...
It is recommended that control wiring is rated for 600 V for 480 V and 600 V drives and 300 V for 200-240 V drives. • Isolate control wiring from high power components in the drive. • See label inside of panel cover for details. Illustration 3.7: Control Terminals Location EIA-485 terminal Jumper wire TR200 Option Panel Operating Instructions...
If shielded cabling is used, do not connect end of shield to terminal 61. Programming Serial communication point maps, parameter settings, and other details for bypass option functionality are included in the serial communication materials supplied with the unit. TR200 Option Panel Operating Instructions...
Check that overload relay(s) is set for FLA of connected motor. Service factor is built into overload relay. For drive start up procedures, see drive instruction manual. Inspection Prior to Start Up Before applying power to the unit, inspect the entire installation as detailed in table below. TR200 Option Panel Operating Instructions...
Ensure that all operator devices are in OFF position. Main and drive disconnect switches on front of elec- tromechanical bypass panel must be in OFF position. Panel door(s) closed. Keep main disconnect switch in OFF position and apply voltage to option panel. DO NOT operate drive or bypass at this time. TR200 Option Panel Operating Instructions...
Page 26
Check full load amps on input terminals L1, L2, and L3. Verify that current is within FLA of drive and balanced within 3%. If incorrect, see Troubleshooting Section in this manual for isolation procedures. 10. Check full load amps in bypass mode on motor terminals. TR200 Option Panel Operating Instructions...
Page 27
12. Exercise safety circuit and verify that unit stops running. 13. Exercise start/stop circuit and verify that unit starts and stops with system in auto mode of operation. TR200 Option Panel Operating Instructions...
Page 29
The second of the following tables lists common functions for controlling a motor(s) with a bypass and the typical terminal connections used. Commands enable drive functions. Status reports describe conditions but do not enable a function. TR200 Option Panel Operating Instructions...
Page 30
External Inter- lock Term 27 Mode Input External Inter- lock Term 27 digital External Interlock External Inter- input lock Term 29 Mode Output Auto bypass Term 29 digital No Alarm Auto bypass output Table 5.2 TR200 Option Panel Operating Instructions...
If the drive is reinitialized, be sure that these settings are maintained or reset for proper bypass operation. See the mechanical layout diagram inside the cover of the unit for connector locations within the unit. TR200 Option Panel Operating Instructions...
Page 32
Mode Output Input Normally open, dry contact CMS Motor 1, close to select CMS Common Normally open, dry contact CMS common Input Normally open, dry contact CMS Motor 2, close to select Table 5.4 TR200 Option Panel Operating Instructions...
Page 33
Parameter name Value number Value name Function Term 18 digital in- Start Common run/stop Digital I/O Mode External Interlock Term 27 Mode Input External Interlock Term 27 digital in- External Inter- External Interlock lock Table 5.6 TR200 Option Panel Operating Instructions...
Common run/stop is enabled by factory default. When used with the run permissive function, common run/stop permits run request operation in bypass. TR200 Option Panel Operating Instructions...
Wire the input run permission to connector X55, terminals 1 and 2 per the system application. Disable Run Permissive • Run permissive is enabled by factory default when ordered. • To disable the run permissive function, jumper between terminals 1 and 2 on connector X55. TR200 Option Panel Operating Instructions...
It is highly recommended to operate in the manual factory setting to prevent the risk of damage to the motor. TRIP MANUAL AUTO TEST RESET 98NO 95NC 97NO 96NC Illustration 5.5: Sample Overload Device TR200 Option Panel Operating Instructions...
The fault contacts are fail-safe, meaning that if power is removed a fault condition is automatically reported. Fault status is not monitored in bypass operation. TR200 Option Panel Operating Instructions...
(M1 and M2 contactors), connected to the full-speed bypass (M3 contactor), or disconnected from both. The test position allows for operation in bypass while still providing power to the drive (M1 and M3). See figure below. Illustration 5.6: Basic 3-contactor Bypass Functions TR200 Option Panel Operating Instructions...
Terminal functions are programmed in the 5-00 parameter group. (See table below for factory default parameter settings for drives with an ECB.) Bypass functions are programmed in the 31-00 pa- rameter group (see later this chapter). See the drive’s supporting materials for detailed programming instruc- tions. TR200 Option Panel Operating Instructions...
Trane website. • Also provided are two Form C relay outputs that are in various locations depending upon the drive configuration and size. See the drive support materials for detailed instructions. Illustration 6.2: Drive Control Terminals TR200 Option Panel Operating Instructions...
Page 41
68 (+), 69 (-) RS-485 interface. When the drive is connected to an RS-485 serial communication bus, a drive control card switch is provided for termination resistance. ON for termination and OFF for no termination. See drive support materials for details. Table 6.2 TR200 Option Panel Operating Instructions...
X59 for reporting the bypass mode of operation, either drive mode or running in bypass. See the next table for ECB control card terminal types and functions. Illustration 6.3 Terminal X58 Terminal X56 Terminal X57 Terminal X59 TR200 Option Panel Operating Instructions...
Page 44
Common for binary I/O Relay Output Term. Function N.O. contact for running in bypass or drive Relay output for user N.O. contact for running in bypass or drive Relay output for user 3-12 Factory use only Table 6.3 TR200 Option Panel Operating Instructions...
CANCEL to remain in by- pass mode. 4. Press STATUS key to return to drive status display. Table 6.4 NOTE PRESSING THE INFO KEY AT ANY TIME DISPLAYS TIPS AND GUIDELINES FOR PERFORMING THE FUNCTION CURRENTLY ACTIVATED. Illustration 6.5 TR200 Option Panel Operating Instructions...
0-9. Selected digit is inverse highlighted. 9. Press OK key to activate selection or CANCEL key to cancel. 10. Press STATUS key to return to operational display data or BACK key to return to parameter menu options. Table 6.5 TR200 Option Panel Operating Instructions...
Drive mode.The motor is connected to and controlled by the drive. Contactors M1 (optional) and M2 are closed while contactor M3 is open. (Contactor M1 for test mode is only present in the 3-contactor configuration.) The motor will not run until a run command is present. TR200 Option Panel Operating Instructions...
Page 48
Read only display which shows the bypass status in hex. See next table for details. 0, 216-1 (default value is 0) 31-11 Bypass Running Hours Read only display which shows by- pass running hours. Table 6.7 TR200 Option Panel Operating Instructions...
If the fault clears before the time delay is complete, the motor remains operating in drive mode. This allows temporary faults, such as a momentary under or over voltage, to clear without transferring the system to bypass. TR200 Option Panel Operating Instructions...
• Verify that the drive is programmed for the run permissive function. See the drive support materials for programming the run permissive function. TR200 Option Panel Operating Instructions...
RECT OVERLOAD CONDITION AND LET OVERLOAD AND MOTOR RETURN TO NORMAL OPERATING TEMPERA- TURE BEFORE RESETTING. SEE MOTOR MANUFACTURER’S RECOMMENDATIONS FOR TIME BETWEEN START ATTEMPTS. FAILURE TO CORRECT OVERLOAD CONDITION AND LET MOTOR RETURN TO NORMAL OPERATING TEMPERATURE COULD CAUSE MOTOR DAMAGE. TR200 Option Panel Operating Instructions...
For technicians familiar with connecting to drive terminals 12 and 27 for safety interlock, be aware that ECB bypass operation will NOT stop with the external fault report. Use terminals 1 and 2 on connector X57, as indicated, for bypass control. TR200 Option Panel Operating Instructions...
ECB Fault Reporting General Information The ECB monitors bypass contactors M2 and M3 and reports failures to the drive for display and external re- porting. The drive also monitors the ECB card for bypass communication errors. TR200 Option Panel Operating Instructions...
Page 54
The drive monitors the ECB card communication and detects when communication stops. An ECB card failure or communication error could cause this. Contact Traneusing the phone number on the back of this manual for technical support if this happens. Fault Reporting Function Setup • Automatic function. No set up required. TR200 Option Panel Operating Instructions...
The single motor option is when a drive is running one motor or the motor is operating in bypass mode. The drive and motor are normally the same hp. The FLA of the motor must be less than or equal to the maximum output current of the drive. TR200 Option Panel Operating Instructions...
The motor 1 position selects motor 1, and the motor 2 position selects motor 2. • When SW2 is in the auto position, either motor can be selected remotely. (Do not close both contacts at once.) TR200 Option Panel Operating Instructions...
Page 57
This optional switch is provided for contact motor select available with the EMB option when two equally rated motors are operated by one drive. The panel mounted Motor 1/ Auto/Motor 2 selector switch provides local control of motor 1 or 2 along with an auto setting that allows for remote motor selection. TR200 Option Panel Operating Instructions...
This time delay can be adjusted using parameter 31-01. Bypass Activates in: Indicates the number of seconds left until the system automatically activates Bypass Mode. Time delay can be adjusted using parame- ter 31-02. Table 8.2 TR200 Option Panel Operating Instructions...
Page 59
OL tripped A tripped OL will disable the mo- Perform pre-startup check list tor from running. Verify that OL and set OL per instructions. relay is in normal operating po- sition per manual. Table 8.3 TR200 Option Panel Operating Instructions...
Page 60
Drive is overloaded for the ap- Perform startup and verify plication. drive current is within speci- fications. If not reduce the load on the motor. Loose connections Perform pre-startup check for Tighten loose connections. loose connections. Table 8.4 TR200 Option Panel Operating Instructions...
Page 61
Start Up Troublehooting TR200 Option Panel Operating Instructions...
Page 62
Start Up Troublehooting TR200 Option Panel Operating Instructions...
Need help?
Do you have a question about the TR200 and is the answer not in the manual?
Questions and answers