CAUTION
Carry out No Flow tuning before setting the PI controller parameters!
No Flow Detection
is based on the measurement of speed and power. For a certain speed, the adjustable fre-
quency drive calculates the power at no-flow.
This coherence is based on the adjustment of two sets of speed and associated power at no-flow. By monitoring
the power, it is possible to detect no-flow conditions in systems with fluctuating suction pressure, or if the pump
has a flat characteristic towards low speed.
CAUTION
If to use the integrated PI controller, carry out No Flow tuning before setting the PI controller parameters!
Low speed detection:
Low Speed Detection
gives a signal if the motor is operating with minimum speed as set in par.4-11
Low Limit [RPM]
or par.4-12
vidual selection not possible).
The use of Low Speed Detection is not limited to systems with a no flow situation, but can be used in any system
where operation at minimum speed allows for a stop of the motor until the load calls for a speed higher than
minimum speed, e.g., systems with fans and compressors.
CAUTION
In pump systems, ensure that the minimum speed in par.4-11
Low Limit [Hz]
has been set high enough for detection as the pump can run with a rather high speed even with valves
closed.
Dry pump detection:
No Flow Detection
can also be used for detecting if the pump has run dry (low power consumption-high speed).
Can be used with both the integrated PI controller and an external PI controller.
The condition for Dry Pump signal:
-
Power consumption below no flow level
and
-
Pump running at maximum speed or maximum reference open-loop, whichever is lowest.
TR200 Programming Guide
Motor Speed Low Limit
[Hz]. Actions are common with No Flow Detection (indi-
Parameter Description
Motor Speed Low Limit [RPM]
Motor Speed
or par.4-12
Motor Speed
4-185