Parameter Description
23-53 Energy Log
Range:
0 N/A*
[0 - 4294967295 N/A]
NOTE
All counters are automatically reset when changing the setting in par.23-50
update of the counters will stop at maximum value.
NOTE
When mounting an Analog I/O MCB109 option card, a battery backup of the date and time is included.
23-54 Reset Energy Log
Option:
[0] *
Do not reset
[1]
Do reset
4-202
Function:
Array with a number of elements equal to the number of counters ([00]-
[xx] below parameter number in display). Press OK and Step between
elements by means of
and
Array elements:
Data from latest period is stored in the counter with the highest index.
At power-down, all counter values are stored and resumed at next pow-
er-up.
Function:
Do reset
Select
[1] to reset all values in the Energy Log counters shown
in par.23-53
Energy
Log. After pressing OK, the setting of the parameter
value will automatically change to
buttons on the Local Control Panel.
Energy Log
Resolution. At overflow the
Do not reset
[0].
TR200 Programming Guide