How to Program
Green LED/On: Control section is working.
Yellow LED/Warn.: Indicates a warning.
Flashing Red LED/Alarm: Indicates an alarm.
Keys
Menu keys
The menu keys are divided into functions. The keys
below the display and indicator lamps are used for
parameter set-up, including choice of display indica-
tion during normal operation.
[Status]
indicates the status of the adjustable frequency drive and/or the motor. Three different readouts can be chosen
by pressing the [Status] key:
5 line readouts, 4 line readouts or Smart Logic Control.
[Status]
Use
for selecting the mode of display or for changing back to display mode from either the quick menu
mode, main menu mode or alarm mode. Also use the [Status] key to toggle single or double readout mode.
[Quick Menu]
allows quick set-up of the adjustable frequency drive. The most common TR200 functions can be program-
med here.
The [Quick Menu] consists of:
My Personal Menu
-
Quick Set-up
-
Function Set-up
-
Changes Made
-
Loggings
-
The Function Set-up provides quick and easy access to all parameters required for the majority of TR200 appli-
cations including most VAV and CAV supply and return fans, cooling tower fans, primary, secondary and
condenser water pumps and other pump, fan and compressor applications. Among other features, it also in-
cludes parameters for selecting which variables to display on the keypad, digital preset speeds, scaling of analog
references, closed-loop single zone and multi-zone applications and specific functions related to fans, pumps
and compressors.
The Quick Menu parameters can be accessed immediately unless a password has been created via par.
0-60
Main Menu
Password, par.0-61
par.0-66
Access to Personal Menu w/o
It is possible to switch directly between Quick Menu mode and Main Menu mode.
[Main Menu]
is used for programming all parameters. The main menu parameters can be accessed immediately unless a
password has been created via par.0-60
3-4
Access to Main Menu w/o
Password, par.0-65
Password.
Main Menu
Password, par.0-61
Personal Menu Password
Access to Main Menu w/o Pass-
TR200 Programming Guide
or