Trane TR200 Programming Manual page 66

Hide thumbs Also See for TR200:
Table of Contents

Advertisement

1-62 Slip Compensation
Range:
0 %*
[-500 - 500 %]
1-63 Slip Compensation Time Constant
Range:
Applica-
[0.05 - 5.00 s]
tion de-
pend-
ent*
1-64 Resonance Dampening
Range:
100 %* [0 - 500 %]
1-65 Resonance Dampening Time Constant
Range:
5 ms*
[5 - 50 ms]
1-7* Start Adjustments
Parameters for setting special motor start features.
1-71 Start Delay
Range:
0.0 s*
[0.0 - 120.0 s]
1-73 Flying Start
Option:
TR200 Programming Guide
Function:
Enter the % value for slip compensation to compensate for tolerances in
the value of n M,N . Slip compensation is calculated automatically, i.e., on
the basis of the rated motor speed n M,N .
Function:
Enter the slip compensation reaction speed. A high value results in slow
reaction, and a low value results in quick reaction. If low-frequency res-
onance problems arise, use a longer time setting.
Function:
Enter the resonance dampening value. Set par.1-64
ening
and par.1-65
Resonance Dampening Time Constant
nate high-frequency resonance problems. To reduce resonance oscilla-
tion, increase the value of par.1-64
Function:
Set par.1-64
Resonance Dampening
Time Constant
to help eliminate high-frequency resonance problems.
Enter the time constant that provides the best dampening.
Function:
The function selected in par.1-80
period.
Enter the time delay required before commencing acceleration.
Function:
This function makes it possible to catch a motor that is spinning freely
due to a line drop-out.
When par.1-73
Flying Start
tion.
Search direction for flying start is linked to the setting in par.4-10
Speed
Direction.
Clockwise
[0]: Flying start search in clockwise direction. If not successful,
a DC brake is carried out.
Both Directions
[2]: The flying start will first make a search in the direction
determined by the last reference (direction). If unable to find the speed,
it will search in the other direction. If not successful, a DC brake will be
Parameter Description
Resonance Damp-
Resonance
Dampening.
and par.1-65
Resonance Dampening
Function at Stop
is active in the delay
is enabled, par.1-71
Start Delay
to help elimi-
has no func-
Motor
4-29