21-64 Ext. 3 Dif. Gain Limit
Range:
5.0 N/A* [1.0 - 50.0 N/A]

Main Menu - Application Functions - TR200 - Group 22

This group contains parameters used for monitoring TR200 applications.
22-00 External Interlock Delay
Range:
0 s*
[0 - 600 s]
22-2* No-Flow Detection
The adjustable frequency drive includes functions for detecting if the load conditions in the system allow the
motor to be stopped:
*Low Power Detection
*Low Speed Detection
One of these two signals must be active for a set time (par.22-24
place. Possible actions to select (par.22-23
No Flow Detection:
This function is used for detecting a no flow situation in pump systems where all valves can be closed. Can be
used both when controlled by the integrated PI controller in the adjustable frequency drive or an external PI
controller. The actual configuration must be programmed in par.1-00
Configuration mode for
-
Integrated PI Controller: Closed-loop
-
External PI Controller: Open-loop
4-184
Function:
See par.21-24
Ext. 1 Dif. Gain Limit
Function:
Only relevant if one of the digital inputs in parameter group 5-1* has
External Interlock
been programmed for
will introduce a delay after the signal has been removed from the digital
input programmed for External Interlock, before a reaction takes place.
No-Flow
Function): No action, Warning, Alarm, Sleep Mode.
for details.
[7]. The external interlock timer
No-Flow
Delay) before selected action takes
Configuration
Mode.
TR200 Programming Guide