Trane TR200 Programming Manual page 72

Hide thumbs Also See for TR200:
Table of Contents

Advertisement

2-04 DC Brake Cut-in Speed [Hz]
Range:
Applica-
[Application dependant]
tion de-
pend-
ent*
2-1* Brake Energy Funct.
Parameter group for selecting dynamic braking parameters. Only valid for drives with brake chopper.
2-10 Brake Function
Option:
[0] *
Off
[1]
Resistor brake
[2]
AC brake
2-11 Brake Resistor (ohm)
Range:
Applica-
[Application dependant]
tion de-
pend-
ent*
2-12 Brake Power Limit (kW)
Range:
Applica-
[Application dependant]
tion de-
pend-
ent*
For 200–240 V units:
For 380–480 V units
For 380–500 V units
For 575–600 V units
This parameter is only active in adjustable frequency drives with an integral dynamic brake.
TR200 Programming Guide
Function:
Function:
No brake resistor installed.
Brake resistor incorporated in the system, for dissipation of surplus brak-
ing energy as heat. Connecting a brake resistor allows a higher DC link
voltage during braking (generating operation). The resistor brake func-
tion is only active in adjustable frequency drives with an integral dynamic
brake.
AC Brake will only work in Compressor Torque mode in par.1-03
Characteristics.
Function:
Function:
390 2 ×
dutytime
P resistor
=
R
× 120
778 2 ×
dutytime
P resistor
=
R
× 120
810 2 ×
dutytime
P resistor
=
R
× 120
943 2 ×
dutytime
P resistor
=
R
× 120
Parameter Description
Torque
4-35

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents