Timers must return a value. All timer commands must have "BLKV1 = the variable"
e.g.BLKV1 = tpause[1]. Value returned is the same as tget[1]. Timers count in seconds.
Maximum of 20 timers available.
43-TV-25-35 GLO Iss.4 Dec 06 UK
A5E01001767-04
Full Maths & Script Processing
Compare & Convert
%RHc
%RHf
C2f
F2c
Hi
Hi4
Inside
Lo
Lo4
Outside
Over
Under
Timers
Tget
Tpause
Treset
Trun
Table 14.3 :
Syntax
rhc[x,y]
Returns % Relative Humidity with y as the dry bulb
temperature in degrees C, and x the wet bulb tem-
perature in degrees C
rhf[x,y]
Returns % Relative Humidity with y as the dry bulb
temperature in degrees F, and x the wet bulb tem-
perature in degrees F
c2f[x]
Converts a temperature in C to one in F
f2c[x]
Converts a temperature in F to one in C
hi[x,y]
Returns the larger value of x & y
hi4[x,y,x1,y1]
Returns the larger value of x, y, x1,y1
inside[x,y,z]
Returns x if between y & z, otherwise returns 0.
lo[x,y]
Returns the lower value of x & y
lo4[x,y,x1,y1]
Returns the lower value of x, y, x1, y1
outside[x,y,z]
Returns x if outside of y & z, otherwise returns 0
over[x,y]
Returns x if it's larger than y, otherwise returns 0
under[x,y]
Returns x if it's less than y, otherwise returns 0.
Table 14.4 :
Syntax
tget[x]
Returns the elapsed time of timer x since start
tpause[x]
Pauses the timer x
treset[x]
Resets the timer x
trun[x,y]
Starts the timer x in y mode. (Mode 1 = reset to
0 and run, Mode 0 = resume from previous
value)
Description
Description
237