Siemens SIREC D200 Manual page 58

Display recorders
Hide thumbs Also See for SIREC D200:
Table of Contents

Advertisement

(Main Menu > Configure > Setup > Edit Setup> Field IO > Analogue In)
Press the Analogue In button to display all the analogue inputs available.
Click on individual Analogue In number to set up each channel profile. Each channel has a
list of menu items to be configured.
Refer to connection details and
52
Analogue In Menu
• Enabled - Toggle On and Off.
• Type - Select this for a list of available Signal Inputs.
• Sample Rate - Select this for a list of available Analogue Input sample speeds. A Fast
Scanning range of 50Hz (20ms) is available as a firmware option (not available for the
SIREC D200 recorder)
Arranged in 2 banks of 3 inputs, and sample rate must be the same within each bank,
SIREC D200 recorder
only for
• Range (Ohms, Volts and Amps only) - Toggle between Preset and User Defined. The
Preset option will make available a list of Range Types or select User Defined to specify
High and Lower Limits.
• Range Type (Ohms, Volts and Amps only) - Only available when Range is set to Pre-
set. Select for a list of available ranges. The factory default range is +/-12V.
"User Defined Maximum Input Ranges" on page 220
• Damp Level - The damping filter is an advanced algorithm offering improved response
over more traditional methods. It works by producing configuable levels of damping -
but at the same time being able to respond rapidly to large input changes. Enter the
Damp Level in Engineering Units.
Power up
"Analogue Input Channel Numbers" on page
See "Firmware Credit System" on page 167.
.
.
17..
Menu path to current menu
The Analogue In screen
displays all the available
Analogue Input channels.
Each channel displays its'
individual settings.
Select a numbered chan-
nel to edit the configura-
tion of each input
See
43-TV-25-35 GLO Iss.4 Dec 06 UK
A5E01001767-04