In this menu there is a button for each slot for Cold Junction Calibration. Calibration is per-
formed per slot/card.
(Configure > Setup > Edit Setup> General > Factory > Demo Traces)
A set of demo traces available for demonstration or simulation purposes when no Analogue
cards are fitted.
Options for each demo trace are:
(Configure > Setup > Edit Setup> General > Factory > Reset Setup)
This will remove the current setup from the recorder and return to the default setup. When
you select this button the "Reset Setup Warning" box will appear with a message: "Are you
sure you want to clear your current setup? This is irreversible and will restart the re-
corder". Select OK to reset the setup or Cancel to ignore and return to the Factory menu.
(Configure > Setup > Edit Setup> General > Factory > Delete All Data)
This button will delete all data from the internal memory. When you select this button the
"Reset Data Warning " box will appear with a message: "This will delete ALL log and
chart data, taking approx 80 seconds to complete and will restart the recorder during
the process". 80 seconds is an approximate time depending on the size of the internal
memory. Select OK to proceed. This is an irreversible procedure.
96
• Select the desired slot button. If a CJC connector is not fitted a message box will
appear.
• The CJC temperature reading is displayed in the CJ Temp column.
• If the known temperature is different to the recorder's reading an Offset can be entered
to make an adjustment to future values. The Cold Junction temperature should be
measured at the point where the thermocouple is connected in the terminal block.
Ensure the measured temperature is accurate to within 0.1
• Enter the difference between the CJ Temp on the recorder and the measured reading
as the Offset Value. The offset is added to all future readings and displayed in the Cal-
ibrated CJ Temp column.
• The Measured Temp column will display the actual temperature using the Calibrated
CJC Temp, on channels with T/C fitted. For more details of how a thermocouple works,
"Appendix C: Thermocouple Connections" on page 247.
refer to
• Select the tick box to go back and the Finish button to Commit, Discard or Commit
Later.
Demo Traces
Demo traces are deactivated and no simulation traces are
• No Simulation -
available.
• Simulate if board not fitted -
not fitted in one of the top two slot positions.
Reset Setup
Delete All Data
Power up
Simulation is activated when an Analogue In card is
°
C.