Configuring Serial Line And Modbus Rtu; Figure 24 Modbus Rtu Settings Page - Vaisala Optimus OPT100 Installation Manual

Dga monitor for transformers
Hide thumbs Also See for Optimus OPT100:
Table of Contents

Advertisement

5.9 Configuring Serial Line and Modbus RTU
Figure 24 Modbus RTU Settings Page
This procedure configures the settings of the RS-485 line and the Modbus RTU
protocol.
1. In the user interface, select Settings > Network > Modbus.
2. Select Baud Rate for the connection. Available options are:
• 4800
• 9600
• 19200
• 38400
• 57600
• 115200
3. Select Transmission Mode, 8E1 or 8N2.
4. Enter the Modbus Slave ID for the DGA monitor. Range 1 ... 247.
5. Click Apply to save your changes.
Chapter 5 – Commissioning
55