Initializing Dga Monitor - Vaisala Optimus OPT100 Installation Manual

Dga monitor for transformers
Hide thumbs Also See for Optimus OPT100:
Table of Contents

Advertisement

OPT100 Installation Guide
3. To set the time manually:
a. Change Set date and time to Manually.
b. Select or enter the current date in the Date field. The format is yyyy-mm-dd.
c. Enter the current time in the Time field. The field is in 24-hour clock notation in the
form hh:mm.
d. Select Apply to save the manually set time.
4. To set up time synchronization with a Network Time Protocol (NTP) server:
NTP synchronization requires that the network connection is configured and
the IP address of the NTP server is reachable.
a. Change Set date and time to Use NTP.
b. Enter the IP address of the NTP server in the NTP server field.
c. Select Apply to start time synchronization. Status of time synchronization is shown
below the NTP server field. If the status shows Connecting... and does not progress
to Synchronizing time... even after waiting for a minute, verify that the network
connection is working and configured, and the IP address of the NTP server is
correctly entered.
d. Wait for the message Time successfully synchronized to appear.
5.8 Initializing DGA Monitor
• 5 mm hex key
Before starting the initialization, make sure that:
• DGA monitor is fully installed and wired.
• All oil connections are completed.
• DGA monitor is turned on.
• You are connected to the user interface with a web browser.
You must have physical access to the DGA monitor enclosure and the oil valves on
the transformer. Do not try to perform the initialization remotely.
You can stop the initialization sequence at most phases by selecting Control >
Cancel.