Configuring Relays; Figure 28 Relay Settings Page - Vaisala Optimus OPT100 Installation Manual

Dga monitor for transformers
Hide thumbs Also See for Optimus OPT100:
Table of Contents

Advertisement

3. For each alert you want to configure, enter the
a. Enter the Caution Limit in ppm. This is the lower limit that triggers an alert with
caution severity.
b. Enter the Alarm Limit. Alarm limit should be higher than the caution limit.
c. Set the alert to On to enable it.
Settings are applied immediately.
It is possible to have only caution or alarm severity active. If you leave a limit
value empty or enter a zero, the corresponding severity will not be active for
that alert.
5.13 Configuring Relays
Figure 28 Relay Settings Page
1. In the user interface, select Settings > Relays.
Chapter 5 – Commissioning
59

Advertisement

Table of Contents
loading

Table of Contents