2.8.1 Installation Location of DGA monitor
The DGA monitor can be attached to the transformer chassis or to its immediate vicinity. The
location must fulfill the following requirements:
• The location must be close to the oil connections to minimize the length of the oil lines.
The maximum length of the lines is 10 m (33 ft) each.
• The location must be safely accessible from the floor without the need to climb or reach.
• There must be enough room and suitable supporting structures to install the DGA monitor
in a vertical orientation. The DGA monitor must not be tilted more than 5 degrees.
• If the Ground Mounting Set is used, there must be a level concrete surface that is at least
100 mm thick.
If you have many suitable locations, prefer the following:
• Locations that are protected from rain and solar radiation.
• Locations where the vibration and heat from the transformer are not directly conducted
to the DGA monitor.