M211982EN-C Quick Guide â Vaisala HUMICAP Humidity and Temperature Probes HMP4, HMP5, HMP7, HMP8, TMP1...
Page 2
Street address: Vanha Nurmijärventie 21, FI-01670 Vantaa, Finland Mailing address: P.O. Box 26, FI-00421 Helsinki, Finland Phone: +358 9 8949 1 Visit our Internet pages at www.vaisala.com. local rules and regulations No part of this manual may be applicable at any given time, and...
Page 3
Table of Contents English..........................5 日本語........................... 17...
2 m (6.5 ft) cable between the probe body and the probe head. The probes are compatible with Vaisala Indigo ™ transmitters. They can also be connected to Vaisala Insight software for configuration, diagnostics, and temporary online monitoring.
32 mm 27 mm [in] Figure 2 HMP4 Probe Head Dimensions Vaisala HUMICAPâ Humidity and Temperature Probe HMP4 is designed for high-pressure applications such as compressed air systems in maritime, breathing air, and industrial applications, where measurement performance and chemical tolerance are essential.
Page 7
[in] Figure 4 HMP7 Probe Head Dimensions Vaisala HUMICAPâ Humidity and Temperature Probe HMP7 is designed for applications which involve constant high humidity or rapid changes in humidity such as drying and test chambers, combustion air and other humidifiers and meteorological measurements where measurement performance and chemical tolerance are essential.
Page 8
Vaisala HUMICAPâ Humidity and Temperature Probe HMP8 is designed for pressurized applications in compressed air systems, refrigerant dryers, environmental chambers and other pressurized industrial applications where easy insertion and removal of the probe and adjustable installation depth into the pipeline are needed.
Page 9
M12/5 M12/5 Male Connector Figure 7 Probe Body Pin # Function Notes Wire Colors in Vaisala Cables Power supply Supply voltage: Brown • HMP7: 18 ... 30 VDC • Other models: 15 ... 30 VDC Typical current 10 mA, max. 500 mA.
Attaching Probes to Indigo Transmitters Figure 8 Attaching the Probe to Indigo 200 Series 1. Insert the probe or the connection cable into the transmitter's connector. Use of connection cable is recommended for strain relief. 2. Turn the locking wheel of the transmitter to lock the probe or cable in place. Do not turn the probe or the cable itself, as that will damage the connectors.
Let the cable hang loosely to prevent condensed water from running along the cable to the probe head. Attach the probe body to a wall or other surface using the two mounting clips (Vaisala item 243257SP) supplied with the probe. Each clip attaches to the installation surface with one screw (screw hole Ø...
• Configure probe features such as measurement filtering, chemical purge, heating, and serial communication Download Vaisala Insight software at www.vaisala.com/insight. The probe can be connected to Vaisala Insight software using a Vaisala USB cable (no. 242659). Connecting to Insight Software •...
Page 13
Modbus Serial Interface Settings Table 1 Default Serial Interface Settings Property Description/Value Bit rate 19200 Parity None Data bits Stop bit Flow control None You can use up to ten probes on the same RS-485 line. You must configure each probe on the line to have a different Modbus address.
Register Address Register Description Data Format Metric Unit Number (Hexadecimal) (Decimal) Floating Point Values 0018 Water vapor saturation 32-bit float pressure 001A Enthalpy 32-bit float kJ/kg 001E Dew point temperature 32-bit float °C difference 0020 Absolute humidity at 32-bit float 0040 Water vapor mass 32-bit float...
Page 15
Compensation Setpoints 0334 Temperature 32-bit float Unit: °C compensation setpoint. If a value is written to this register, probe uses it when calculating relative humidity instead of its own measurement. When probe heating is in use, temperature must be written to this register to enable relative humidity measurement.