22
Zenith ZBTS T-series 100 – 600 A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N

2.4 Bypass and ATS Switches, Features

Features
Ampere sizes available
Rated voltage, three phase
Rated voltage, single phase
Rated frequency
Phase system
Number of poles
Neutral configuration
Switched
Overlapping
Product type
Open transition
Delayed transition
(I - O - II or II - O - I)
Voltage and frequency settings
Pick up Voltage Source 1
Drop out Voltage Source 1
Pick up Voltage Source 2
Drop out Voltage Source 2
Pick up Frequency Source 1
Drop out Frequency Source 1
Pick up Frequency Source 2
Drop out Frequency Source 2
Time delay settings
Override momentary
Source 1 Outage, sec
Transfer from source 1
to source 2, sec
Level 4 controls (TOUCH)
S1
O
S2
l
ll
LOAD
l
O
ON
OFF
IEC: 200...630 A
UL: 100...600 A
200...480 Vac
200...240 Vac
50 / 60 Hz
Single and Three
3 and 4
71...99 %, 101...119 %
70...98 %, 102...120 %
71...99 %, 101...119 %
70...98 %, 102...120 %
80,5...99,5 %, 100,5...119,5 %
80...99 %, 101...120 %
80,5...99,5 %, 100,5...119,5 %
80...99 %, 101...120 %
0...60
0...3600
Continued on next page
!
AUTO
ll
ON
Yes
Yes
Yes
Yes

Advertisement