6

Troubleshooting

Problem
All cubicle types
Switch-disconnector cannot be closed.
Switch-disconnector cannot be opened.
Switch-disconnector cannot be moved to
the earthed position.
Switch-disconnector cannot be moved
from the open to earthed position.
Cable compartment door will not open or
close.
Motor operated switch-disconnector
Switch-disconnector will not close or
open.
Switch-fuse cubicle
Switch-fuse will not close.
ABB
Uniswitc h Operation and
Maintenanc e Manual
Action
Check that the switch is in the open position.
Check that the interlocking selector is in the
'Operation' position.
Turn the operating handle clockwise.
Check that the switch is in the closed position.
Check that the interlocking selector is in the
'Operation' position.
Turn the operating handle anti-clockwise.
Check that the switch is in the open position.
Check that the interlocking selector is in the 'Test'
position.
Turn the operating handle clockwise.
Check that the switch is in the earthed position.
Check that the interlocking selector is in the 'Test'
position.
Turn the operating handle clockwise.
Check that the switch is in the earthed position.
Check that the interlocking selector is in the 'Door
open' position.
Check that the switch is not in the earthed position.
Check that the interlocking selector is in the
'Operation' position.
Check that the auxiliary power supply is connected.
If the switch is in the open position due to a fuse trip or
motor operation, the notch on the operating shaft is to be
turned downwards before the switch can be operated to
the closed position.
Check to see if a fuse has blown.
52
UNI S14GB 05-02