Specifications

7 Specifications
7.1 Electrical Data, 380–480 V
VLT® AQUA Drive FC 202
High/normal load
(High overload=150% current during 60 s,
normal overload=110% current during 60 s)
Typical shaft output at 400 V [kW]
Typical shaft output at 460 V [hp]
Enclosure size
Output current (3-phase)
Continuous (at 400 V) [A]
Intermittent (60 s overload)
(at 400 V) [A]
Continuous (at 460/500 V) [A]
7
7
Intermittent (60 s overload)
(at 460/500 V) [A]
Continuous kVA (at 400 V) [kVA]
Continuous kVA (at 460 V) [kVA]
Maximum input current
Continuous (at 400 V) [A]
Continuous (at 460/500 V) [A]
Maximum number and size of cables
per phase (E1h)
- Mains and motor without brake [mm
- Mains and motor with brake [mm
- Brake or regeneration [mm
Maximum number and size of cables
per phase (E3h)
- Mains and motor without brake [mm
- Mains and motor with brake [mm
- Load share or regeneration [mm
Maximum external mains fuses [A]
Estimated power loss at 400 V [W]
Estimated power loss at 460 V [W]
Efficiency
4)
Output frequency
Heat sink overtemperature trip [°C (°F)]
Control card overtemperature trip [°C (°F)]
Power card overtemperature trip [°C (°F)]
Fan power card overtemperature trip [°C (°F)]
Active in-rush card overtemperature trip
[°C (°F)]
Table 7.1 Technical Specifications, Mains Supply 3x380–480 V AC
32
VLT® AQUA Drive FC 202
HO
315
450
600
900
540
810
416
430
578
520
2
1)
5x240 (5x500 mcm)
(AWG)]
2
1)
4x240 (4x500 mcm)
(AWG)
2
(AWG)
1)
2x185 (2x350 mcm)
2
(AWG)]
1)
6x240 (6x500 mcm)
2
1)
2x185 (2x350 mcm)
(AWG)
2
1)
4x185 (4x350 mcm)
(AWG)
2)
3) 4)
6178
3) 4)
5322
Danfoss A/S © 05/2017 All rights reserved.
N355
N400
NO
HO
355
355
500
500
E1h/E3h
E1h/E3h
658
658
724
987
590
590
649
885
456
456
470
470
634
634
569
569
5x240 (5x500 mcm)
4x240 (4x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
800
6928
6851
5910
5846
0.98
0–590 Hz
0–590 Hz
110 (230)
110 (230)
80 (176)
80 (176)
85 (185)
85 (185)
85 (185)
85 (185)
85 (185)
85 (185)
N450
NO
HO
400
400
600
550
E1h/E3h
745
695
820
1043
678
678
746
1017
516
482
540
540
718
670
653
653
5x240 (5x500 mcm)
4x240 (4x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
800
800
8036
7297
6933
7240
0.98
0.98
0–590 Hz
110 (230)
80 (176)
85 (185)
85 (185)
85 (185)
NO
450
600
800
880
730
803
554
582
771
704
8783
7969
MG22B102