10.9 Leakage Current
Follow national and local codes regarding protective
grounding of equipment where leakage current exceeds
3.5 mA.
Drive technology implies high-frequency switching at high
power. This high-frequency switching generates a leakage
current in the ground connection.
The ground leakage current is made up of several contri-
butions and depends on various system configurations,
including:
•
RFI filtering.
•
Motor cable length.
•
Motor cable screening.
•
Drive power.
Leakage current
Illustration 10.11 Motor Cable Length and pPower Size
Influence the Leakage Current. Power Size a > Power Size b.
The leakage current also depends on the line distortion.
MG22B102
Design Guide
Leakage current
Illustration 10.12 Line Distortion Influences Leakage Current
a
If the leakage current exceeds 3.5 mA, compliance with
EN/IEC61800-5-1 (power drive system product standard)
requires special care.
Reinforce grounding with the following protective earth
connection requirements:
b
•
Motor cable length
•
See EN/IEC61800-5-1 and EN 50178 for further information.
Danfoss A/S © 05/2017 All rights reserved.
Ground wire (terminal 95) of at least 10 mm
AWG) cross-section.
2 separate ground wires both complying with the
dimensioning rules.
THDv=0%
THDv=5%
10
2
(8
85
10