Terminal No.
Type
X540:1 - 8 P24
24 V DC supply voltage for the inputs D 0 to
DI7 and DI/DO8 to DI/DO11
X520:1
DI0
X520:2
DI1
Digital input isolated via optocoupler
X520:3
DI2
X520:4
DI3
X520:5
M1
Ground terminal for digital inputs DI0 to DI3
X520:6
M (GND)
Ground terminal for P24 auxiliary voltage for
digital inputs
X530:1
DI4
X530:2
DI5
Digital input isolated via optocoupler
X530:3
DI6
X530:4
DI7
X530:5
M2
Ground terminal for digital inputs DI4 to DI7
X530:6
M (GND)
Ground terminal for P24 auxiliary voltage for
digital inputs
X541:1
P24
X541:2
DI/DO8
X541:3
DI/DO9
Non-isolated digital inputs/outputs
X541:4
DI/DO10
X541:5
DI/DO11
X541:6
M (GND)
Ground terminal of P24 and ground of digital
inputs/outputs
X521:1
AI 0 +
Analog inputs as differential inputs for the
following ranges:
X521:2
AI 0-
-10 V
+ 4 mA To
X521:3
AI 1 +
-20 mA To
0 mA
X521:4
AI 1-
The voltage/current input selection is made
with switch S500
X521:5
P10
X521:6
M (GND)
Auxiliary voltage ± 10 V (10 mA) for the
connection of a potentiometer for setpoint
specification via an analog input
X521:7
N10
X521:8
M (GND)
X522:1
AO 0V+
X522:2
AO 0 ref.
Analog outputs for the following ranges:
-10 V
X522:3
AO 0A+
+ 4 mA To
X522:4
AO 1V+
-20 mA To
X522:5
AO 1 ref.
0 mA
X522:6
AO 1A+
X522:7
KTY+
KTY84 temperature sensor (0 to 200° C) or
PTC (R
X522:8
KTY-
cold
X542:1
DO 0.NC
Relay output, changeover contact
X542:2
DO 0.COM
Max. switching voltage: 250 V AC, 30 V DC
X542:3
DO 0.NO
Max. switching capacity at 250 VAC:
2000 VA
Max. switching capacity at 30 VDC: 240 W
X542:4
DO 1.NC
Relay output, changeover contact
X542:5
DO 1.COM
Max. switching voltage: 250 V AC, 30 V DC
X542:6
DO 1.NO
Max. switching capacity at 250 VAC:
2000 VA
Max. switching capacity at 30 VDC: 240 W
Customer terminal block with factory settings
To
+ 10 V
+20 mA
+20 mA
To
+20 mA
To
+ 10 V
+ 20 mA
+ 20 mA
To
+ 20 mA
≤ 1.5 kΩ)
Factory setting (default)
ON/OFF1
Increase setpoint / fixed setpoint
bit 0
Decrease setpoint / fixed setpoint
bit 1
Acknowledge fault
Enable inverter
Ready (factory-set as digital output) Inputs/outputs are freely parameterizable
Speed setpoint
Factory setting 0 to 20 mA
Reserved
Speed actual value
Factory setting 0 to 20 mA
Actual motor current value
Factory setting 0 to 20 mA
Checkback:
Enable inverter
Checkback:
No fault in converter
SINAMICS Engineering Manual - May 2008
SINAMICS S150
Engineering Information
Comment
Inputs are freely parameterizable
Converter is at standby and is waiting for
enabling
Inputs are freely parameterizable
Factory-set as input
Factory-set as input
Factory-set as input
Positive differential input for
voltage/current
Negative differential input for
voltage/current
Positive differential input for
voltage/current
Negative differential input for
voltage/current
+ 10 V
Ground terminal for ±10 V
- 10 V
Ground terminal for ±10 V
Analog output voltage +
Common reference point for
current/voltage
Analog output current +
Analog output voltage +
Common reference point for
current/voltage
Analog output current +
The sensor type must be parameterized
NC contact
Common
NO contact
NC contact
Common
NO contact
307/396