Sinamics S120 Chassis (Active Line Modules) - Siemens SINAMICS G130 Engineering Manual

Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Dimension Drawings
Engineering Information

SINAMICS S120 Chassis (Active Line Modules)

Dimension drawing 10, frame size FX:
380 V to 480 V
Front view
Required clearance for ventilation - - - - - -
Line supply connection
Max. connection cross-
M10 screw
section
DIN
NEC, CEC
(No. of holes) DIN
VDE
AWG/MCM
mm²
2 x 185
2 x 350 MCM
SINAMICS Engineering Manual – May 2008
356/396
© Siemens AG
132 - 160 kW
Side view
DC link connection
Max. connection
cross-section
NEC, CEC
VDE
AWG/MCM
mm²
(1)
2 x 185
2 x 350
MCM
Grounding
M10 screw
Max. connection cross-
section
(No. of holes)
DIN
VDE
mm²
(1)
PE
2 x 185
M10 screw
NEC, CEC
(No. of holes)
AWG/MCM
2 x 350 MCM
(2)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g150Sinamics s120Sinamics s120 chassisSinamics s150

Table of Contents