Sinamics S120 Chassis (Active Interface Modules) - Siemens SINAMICS G130 Engineering Manual

Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Dimension Drawings
Engineering Information

SINAMICS S120 Chassis (Active Interface Modules)

Dimension drawing 6, frame size FI:
380 V to 480 V
Side view
Required clearance for ventilation - - - - - -
Power supply connection / load
Max. connection cross-
M10 screw
section
DIN
NEC, CEC
(No. of holes)
VDE
AWG/MCM
mm²
2 x 185
2 x 350 MCM
SINAMICS Engineering Manual – May 2008
352/396
© Siemens AG
132 - 160 kW
Front view
(1)
Grounding
Max. connection cross-
section
DIN
NEC, CEC
VDE
AWG/MCM
mm²
PE1
2 x 185
2 x 350 MCM
M10 screw
(No. of holes)
(2)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g150Sinamics s120Sinamics s120 chassisSinamics s150