Auxiliary Power Requirements - Siemens SINAMICS G130 Engineering Manual

Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Auxiliary power requirements

Cabinet Modules require an auxiliary energy supply to function properly. This power requirement must be included in
the configuration and supplied from an external source.
Please ask your Siemens contact for a solution.
Line Connection Modules
The auxiliary voltage for the Line Connection Modules is connected directly to input terminals. The following
components require auxiliary power:
230 V AC
Cabinet ventilation / circuit breaker
Fuse protection of 16 A must be provided on the plant distribution board.
Order No.
Supply voltage 380 V - 480 V 3AC
6SL3700-0LE32-5AA0
6SL3700-0LE34-0AA0
6SL3700-0LE36-3AA0
6SL3700-0LE38-0AA0
6SL3700-0LE41-0AA0
6SL3700-0LE41-3AA0
6SL3700-0LE41-6AA0
6SL3700-0LE42-0AA0
6SL3700-0LE42-0BA0
6SL3700-0LE42-5BA0
6SL3700-0LE43-2BA0
Supply voltage 500 V - 690 V 3AC
6SL3700-0LG32-8AA0
6SL3700-0LG34-0AA0
6SL3700-0LG36-3AA0
6SL3700-0LG38-0AA0
6SL3700-0LG41-0AA0
6SL3700-0LG41-3AA0
6SL3700-0LG41-6AA0
6SL3700-0LG42-0BA0
6SL3700-0LG42-5BA0
6SL3700-0LG43-2BA0
1)
Power requirement of contactors / circuit breaker and fans for degree of protection IP23, IP43, IP54 (in combination with Basic
Line Modules)
Frame size
Rated current
FL
FL
GL
HL
JL
JL
JL
KL
KL
KL
LL
FL
FL
GL
HL
JL
JL
JL
KL
KL
LL
SINAMICS S120 Cabinet Modules
Engineering Information
Current requirement 230 V AC 50/60 Hz
I
Making current Holding current
rated
[A]
[A]
250
3.6
400
3.6
630
3.6
800
10.8
1000
0.5
1250
0.5
1600
0.5
2000
0.5
2000
0.5
2500
0.5
3200
0.5
280
3.6
400
3.6
630
3.6
800
10.8
1000
0.5
1250
0.5
1600
0.5
2000
0.5
2500
0.5
3200
0.5
SINAMICS Engineering Manual - May 2008
1)
Fan
[A]
[A]
0.04
--
0.04
--
0.04
--
0.12
--
0.06
1.07
0.06
1.07
0.06
1.07
0.06
2.14
0.06
2.14
0.06
2.14
0.04
2.14
0.04
--
0.04
--
0.04
--
0.12
--
0.06
1.07
0.06
1.07
0.06
1.07
0.06
2.14
0.06
2.14
0.06
2.14
247/396
© Siemens AG

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g150Sinamics s120Sinamics s120 chassisSinamics s150

Table of Contents