On the line side, either a contactor or a circuit breaker is absolutely essential for the Smart Line Module. With the
selection of option L44 at the Line Connection Module these components are, harmonized with the Smart Line
Module, installed in the Line Connection Module.

DC link fuses

Every Smart Line Module is equipped with DC link fuses. These fuses are located in the power unit of each Smart
Line Module.

Parallel connections of Smart Line Modules

In order to be able to achieve higher output power ratings, it is possible to connect up to four Smart Line Modules
with the same output power rating in parallel. As with other Line Modules, this parallel connection can be realized
with separate Line Connection Modules or one common Line Connection Module for two of the Smart Line Modules.
For this compact design of parallel configurations Smart Line Modules with "mirrored" power connections are
available, comparable to those of the Basic Line Modules. Smart Line Modules, which are mounted to the left of the
Line Connection Module can be identified by the "C" at the last but one position of the order number e.g. 6SL3730-
6TE41-1BC0.
A parallel connection with separate LCMs for each Smart Line Module can be realized with any units of the same
power rating.
Rated power at
Smart Line Modules
400 V
Order No.
[kW]
Supply voltage 380 V – 480 V 3AC (DC link voltage 500 V – 630 V)
250
6SL3730-6TE35-5AA0
355
6SL3730-6TE37-3AA0
500
6SL3730-6TE41-1AA0
500
6SL3730-6TE41-1BA0
500
6SL3730-6TE41-1BC0
630
6SL3730-6TE41-3AA0
630
6SL3730-6TE41-3BA0
630
6SL3730-6TE41-3BC0
800
6SL3730-6TE41-7AA0
800
6SL3730-6TE41-7BA0
800
6SL3730-6TE41-7BC0
Rated Power at
500 V resp. 690 V
[kW]
Supply voltage 500 V – 690 V 3AC (DC link voltage 650 V – 900 V)
325 / 450
6SL3730-6TG35-5AA0
510 / 710
6SL3730-6TG38-8AA0
510 / 710
6SL3730-6TG38-8BA0
510 / 710
6SL3730-6TG38-8BC0
725 / 1000
6SL3730-6TG41-2AA0
725 / 1000
6SL3730-6TG41-2BA0
725 / 1000
6SL3730-6TG41-2BC0
1015 / 1400
6SL3730-6TG41-7AA0
1015 / 1400
6SL3730-6TG41-7BA0
1015 / 1400
6SL3730-6TG41-7BC0
Order number assignment for SLMs
Please note that parallel connections can only be made with Smart Line Modules of exactly the same power rating.
The potential for imbalances in current distribution means that current derating of 7.5 % must be applied and this
must be taken into account when the Modules are dimensioned. Furthermore, to balance the current of the parallel
configuration, a line reactor with a relative short-circuit voltage of 4 % is required for every Smart Line Module. This is
already integrated as standard.
Information on parallel configurations in the chapter "Fundamental Principles and System Description" and also on
the use of DRIVE-CLiQ cables and how to install them in the sections "Information about equipment handling" and
"DRIVE-CLiQ wiring" must be noted.
SINAMICS S120 Cabinet Modules
For parallel configuration, mounted on the right of LCM
For parallel configuration, mounted on the left of LCM
For parallel configuration, mounted on the right of LCM
For parallel configuration, mounted on the left of LCM
For parallel configuration, mounted on the right of LCM
For parallel configuration, mounted on the left of LCM
For parallel configuration, mounted on the right of LCM
For parallel configuration, mounted on the left of LCM
For parallel configuration, mounted on the right of LCM
For parallel configuration, mounted on the left of LCM
For parallel configuration, mounted on the right of LCM
For parallel configuration, mounted on the left of LCM