SINAMICS G150
Engineering Information
Brief overview of SINAMICS G150 parallel converters with production date up to autumn 2007
The following is a short overview of the permissible transformer-converter-motor combinations with SINAMICS G150
parallel converters.
6-pulse configuration
Line reactors required
Symmetrical power cabling
DC links of the two parallel-
connected power units are not
coupled.
The outputs of the two parallel-
connected power units are
connected to a motor with separate
winding systems.
Symmetrical power cabling
Asynchronous motor with two
separate winding systems
Control by SVM + PEM
Maximum motor voltage related to
the line voltage: 97 %
Short overview about the configurations of SINAMICS G150 parallel converters with production date up to autumn 2007
SINAMICS Engineering Manual – May 2008
210/396
© Siemens AG
12-pulse configuration
Decoupling by means of three-
winding transformer.
Symmetrical power cabling
DC links of the two parallel-
connected power units are
coupled.
The outputs of the two parallel-
connected power units are
connected to a motor with separate
winding systems.
Symmetrical power cabling
Asynchronous motor with two
separate winding systems
Control by SVM + PEM
Maximum motor voltage related to
the line voltage: 97 %
12-pulse configuration
Decoupling by means of three-
winding transformer.
Symmetrical power cabling
DC links of the two parallel-
connected power units are
coupled.
The outputs of the two parallel-
connected power units are
connected to a motor with one
common winding system.
Note specifications for minimum
motor cable length or use motor
reactors in the converter
Asynchronous motor with one
common winding system
Control by SVM
Maximum motor voltage related to
the line voltage: 92 %