EMC Installation Guideline
Engineering Information

EMC - compliant construction / installation of a cabinet with a SINAMICS G130 chassis unit

Area of filtered supply
system cables acc. to
Category C3
Line reactor
Line filter ( optional )
acc. to Category C2
Separation plate
Area of filtered supply
system cables acc. to
Categorie C2
Mounting plate for:
- Terminal Module
- Sensor Module
- Control Unit
Fuse
disconnector
EMC shield busbar
PE-busbar
Supply system cable
(unshielded)
Signal cable
and bus cable
(shielded)
Minimum distance between power cables and signal cables: 20 cm to 30 cm
Shield bonding of the motor cable in the converter on an EMC shield busbar using EMC shield
clips and connection of the three symmetrical PE conductors on the PE busbar
Shield bonding of the motor cable on the motor terminal box using EMC cable glands
Shield bonding of the signal, bus, and encoder cables
Shield bonding of the encoder cable on the housing of the speed encoder
Power cables and signal cables cross at an angle of 90°
Signal, bus, and encoder cables in the converter must be routed as close as possible
to the cabinet frame or on grounded plates at a large distance from the power cables
SINAMICS Engineering Manual – May 2008
144/396
© Siemens AG
SINAMICS G130 chassis unit
Motor cable
(shielded)
Speed encoder
Encoder cable
(shielded)
Motor