DRIVE-CLiQ wiring

Cabinet Modules are shipped with all DRIVE-CLiQ connections ready wired within the cabinet. This applies
regardless of any options ordered. DRIVE-CLiQ connections between cabinets cannot be ready wired on shipped
units, as the customer's final implementation requirements cannot be determined from the order and the very wide
range of connection / topology options would make ready wiring impossible. This also applies to connections which
extend beyond a Booksize Cabinet Kit. These cable connections must be ordered separately.
The following cable routes are recommended:
DC P
DC N-
-
U1
-F1
-F2
-X
6
-E1
-X9
-T10
2
-A55
-X2
-U2
-V2
-W2
-T1
-T2
-T3
-X100
X
Cabling route for DRIVE-CLiQ connections with FS FX/GX and HX/JX
The appropriate DRIVE-CLiQ cables can be supplied pre-assembled in defined standard lengths up to 5 m, in meter
lengths up to 70 m or reeled cable with separately available connectors. For ordering information, please refer to the
catalog.
Example of a cable length calculation:
In this example, the Cabinet Modules illustrated in the diagram above must be operated on one Control Unit. The
Control Unit is mounted in the left-hand Motor Module. (The right-hand module also contains a CU320 in the diagram
above. This is merely illustrated for the sake of completeness. DRIVE-CLiQ cannot be used to connect two Control
Units.).
All the connections in the left-hand cabinet are ready made at the factory. In the right-hand cabinet as well, all
DRIVE-CLiQ links, including the connection to the encoder module, have been made in the factory. The only
connection still required is the link between the right-hand power unit and the left-hand Cabinet Module. This can
involve a connection to the Control Unit or require a connection to the power unit as defined by the rules for DRIVE-
DC P
DC N -
-U1
-F1
-F3
-F2
-F
-X
6
-E1
-E2
-F10
-X9
-X2
-U2
-V2
-W2
-T1
-T2
-T3
-A55
-X100
SINAMICS S120 Cabinet Modules
Engineering Information
Cables within the power unit should be routed
according to the specifications for signal cabling in
the equipment manual. A route designed for
minimum cross-interference and thus fault-free
operation is defined within the units. Furthermore,
when units are wired to conform with specifications,
component replacement will not be hindered by cable
routing. Proper cable routing also ensures that
cables are securely mounted.
Cables are routed within the power unit down to the
bottom cabinet cross-beam. From there they can be
taken to the next cabinet. It is always advisable to
install cables along cross-beams to provide EMC
protection.
For planning purposes, the distance between the
terminals on the Control Unit or power unit down to
the bottom cross-beam is 1.5 m for sizes FX and GX
and 1.4 m for sizes HX and JX.
The relevant cabinet width (indicated with x in the
diagram) can be used to plan the connection
distance between cabinets.
One exception is the Basic Line Module in the
version for parallel connection on a Line Connection
Module. The cable length calculation must be based
on 200 mm + x when cables are routed from the left-
hand side. The following can be assumed for routing
to the right: x = cabinet width -200 mm.
For information about Booksize Base Cabinets,
please refer to section "Booksize Base Cabinet/
Booksize Cabinet Kits".