Engineering Information
Technical Data
Order No.
Module
P
kW
DB
(Rated power)
P15
kW
(Maximum power)
Ω
Resistor
Max. current
A
Cable entry
Power connection
Max. connectable
mm²
cable cross-section
Degreee of protection
Width x Height x Depth mm
Approx. Weight
kg
Fits to the Braking
Module with order
number
SINAMICS Engineering Manual – May 2008
236/396
© Siemens AG
500 V – 720 V DC
6SL3000-
6SL3000-
1BE31-
1BE32-
3AA0
5AA0
25
50
125
250
4.4 ± 7.5%
2.2 ± 7.5%
189
378
Cable gland
Cable gland
M50
M50
Bolt
Bolt
M8
M8
50
70
IP20
IP20
740 x 605 x
810 x 1325 x
485
485
50
120
6SL3300-
6SL3300-
1AE31-
1AE32-
3AA0
5 . A0
650 V – 900 V DC
6SL3000-
6SL3000-
1BF31-
1BF32-
3AA0
5AA0
25
50
125
250
6.8 ± 7.5%
3.4 ± 7.5 %
153
306
Cable gland
Cable gland
M50
M50
Bolt
Bolt
M8
M8
50
70
IP20
IP20
740 x 605 x
810 x 1325 x
485
485
50
120
6SL3300-
6SL3300-
1AF31-
1AF32-
3AA0
5 . A0
850 V – 1035 V DC
6SL3000-
6SL3000-
1BH31-
1BH32-
3AA0
5AA0
25
50
125
250
9.8 ± 7.5%
4.9 ± 7.5%
125
255
Cable gland
Cable gland
M50
M50
Bolt
Bolt
M8
M8
50
70
IP20
IP20
740 x 605 x
810 x 1325 x
485
485
50
120
6SL3300-
6SL3300-
1AH31-
1AH32-
3AA0
5 . A0