Factory Settings (Defaults) Of Customer Interface On Sinamics G150 - Siemens SINAMICS G130 Engineering Manual

Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Factory settings (defaults) of customer interface on SINAMICS G150

The following factory settings are provided to simplify configuring the customer interface and commissioning. The
interfaces can also be assigned freely at any time.
Terminal block on TM31
Factory setting
-X520
Optocoupler inputs connected to common
potential
DI0
ON/OFF 1
DI1
Increase setpoint/fixed setpoint 0
DI2
Decrease setpoint/fixed setpoint 1
DI3
Acknowledge fault
-X530
Optocoupler inputs connected to common
potential
DI4
Inverter enable
1)
DI5
OFF 3
DI6
External fault
DI7
-X541
Bidirectional inputs/outputs
DI/DO8
Message: Ready to start
DI/DO9
Not assigned
DI/DO10
Not assigned
DI/DO11
Not assigned
-X542
Relay outputs (changeover contact)
DO 0
Inverter enable (Run)
DO 1
Checkback signal No converter fault
-X521
Analog inputs, differential
AI0+
Analog input for setting speed setpoint
AI0-
AI1+
Analog input reserved
AI1-
-X522
Analog outputs
AO 0V+
AO 0V-
Analog output, actual speed value
AO 0C+
AO 1V+
AO 1V-
Analog output, actual motor current value
AO 1C+
-X522
Thermistor protection
+Temp
-Temp
The factory settings of the bidirectional inputs/outputs are underscored.
1)
A jumper must be inserted here if these inputs are not used
1)
1)
Engineering Information
Comment
Parameters can be set in the firmware to determine whether
operation is via motorized digital potentiometer or fixed setpoint
Converter is at standby and waiting for the enable signal
Ramp-down along quick-stop ramp, only of relevance in
conjunction with the Braking Module
Factory-set as input
Factory-set as input
Factory-set as input
The factory setting for the inputs is 0 to 20 mA.
The factory setting for the inputs is 0 to 20 mA.
The factory setting for the outputs is 0 to 20 mA.
The factory setting for the outputs is 0 to 20 mA.
Input for KTY84 temperature sensor or PTC thermistor
SINAMICS Engineering Manual - May 2008
SINAMICS G150
191/396
© Siemens AG

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g150Sinamics s120Sinamics s120 chassisSinamics s150