Line-Side Components; Line Fuses; Line Reactors - Siemens SINAMICS G130 Engineering Manual

Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

SINAMICS G130
Engineering Information

Line-side components

Line fuses

The combined fuses (3NE1., class gS) for line and semiconductor protection are recommended to protect the
converter. These fuses are specially adapted to provide protection for the input rectifier's semiconductors.
Superfast
Adapted to the overload characteristic of the semiconductor
Low arc voltage
Improved current limiting (lower let-through values)

Line reactors

A line reactor must be installed whenever
the converters are connected to a line supply system with high short-circuit power, i.e. with low line supply
inductance
more than one converter is connected to the same point of common coupling (PCC)
the converters are equipped with line filters for RFI suppression
the converters are equipped with Line Harmonics Filter for reducing harmonic effects on the supply.
The line reactor smoothes the current drawn by the converter and thus reduces harmonic components in the line
current and thus the thermal load on the rectifier and DC link capacitors of the converter. The harmonic effects on the
supply are also reduced, i.e. both the harmonic currents and harmonic voltages in the power supply are attenuated.
Line reactors can be dispensed with only if the supply cable inductance is sufficiently high or the relative short-circuit
*)
power RSC
correspondingly low.
The following values apply to SINAMICS G130 Chassis:
Converter output
SINAMICS G130
< 200 kW
200 kW - 500 kW
> 500 kW
As the configuration of the supply system for operating individual converters is often not known in practice, i.e. the
short-circuit power at the PCC of the converter is not certain, it is advisable to connect a line reactor on the line side
of the converter in cases of doubt.
*)
RSC=Relative Short-Circuit power:
Ratio of the short-circuit power S
converter).
SINAMICS Engineering Manual – May 2008
180/396
© Siemens AG
Line reactor can be
omitted with an RSC
required with an RSC
of
≤ 43
≤ 33
≤ 20
at the PCC to the fundamental frequency apparent power S
k Line
Line reactor is
of
> 43
> 33
> 20
of the connected
Converter