SINAMICS G130
Engineering Information
Line supply voltage
400 V / 500 V / 690 V
With dv/dt filter plus VPL
380 V – 480 V 3AC
500 V – 600 V 3AC
660 V – 690 V 3AC
With sine-wave filter
380 V – 480 V 3AC
500 V – 600 V 3AC
Permissible motor cable lengths for SINAMICS G130 (continued)
Under certain conditions, the permissible cable lengths can be increased even further through the series connection
of two motor reactors. Cable lengths for two motor reactors in series and the corresponding limitations are available
on request.
SINAMICS Engineering Manual – May 2008
186/396
© Siemens AG
Output power at
e.g. Protodur NYCWY
110 kW - 560 kW
110 kW - 560 kW
75 kW - 800 kW
110 kW - 250 kW
110 kW - 132 kW
Maximum permissible motor cable length
Shielded cable
300 m
300 m
300 m
300 m
300 m
Unshielded cable
e.g. Protodur NYY
450 m
450 m
450 m
450 m
450 m