Mitsubishi Electric GOT SIMPLE GS2110-WTBD User Manual page 276

Graphic operation terminal
Hide thumbs Also See for GOT SIMPLE GS2110-WTBD:
Table of Contents

Advertisement

(3) Wiring of the GOT's FG cables and power lines
Actual status
Corrective action
for when they
are bundled
(4) Countermeasures to prevent surges
Actual status
Corrective action
for when surge
suppressors are
not used
Entry columns for surge suppressors
22 - 6
22.1 GOT Restoration Sheets
GOT
FG
Power for the power equipment
GOT
FG
Power for the power equipment
PLC
Output
AC
PLC
Output
AC
The surge suppressor must be
attached close to the load
Model of surge suppressor
The GOT's FG cables and power
lines are bundled together.
Keeping the GOT's FG cables and
power lines away from each other will
help minimize noise interference.
Surge suppressors are used for
wiring equipment (loads) such as no
fuse breakers, electromagnetic
contactors, relays, solenoid valves,
C
L
and induction motors.
R
(When surge suppressors are used,
write their models and the names of
devices for which the surge
suppressors are used in the following
table.)
C
Using surge suppressors on the
L
R
wiring near loads can reduce
interference of the GOT surge.
Device for which the surge suppressor is used
Bundled
Not bundled
Effective
Ineffective
Used
Not used
Effective
Ineffective

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Got simple seriesGot simple gs2107-wtbd

Table of Contents