– For use on a flat surface of a type 4X enclosure indoor use only. – To make wiring connections to the power supply connector, use an AWG 28-12 cable and a tightening torque of min. 0.5 Nm. Mitsubishi Electric, MA00818C...
– Separate the high voltage, signal and supply cables. – Make sure that the voltage and polarity of the power source is correct before connecting the product to the power outlet. – Peripheral equipment must be appropriate for the application and location. Mitsubishi Electric, MA00818C...
1.6 Dismantling and Scrapping – The operator panel or parts thereof shall be recycled according to local regulations. – The following components contain substances that might be hazardous to health and the environment: lithium battery, electrolytic capacitor and display. Mitsubishi Electric, MA00818C...
Dropping it or letting it fall may cause damage. 2. Place the panel cut out where the operator panel is to be situated, draw along the outer sides of the holes and cut according to the markings. Mitsubishi Electric, MA00818C...
Page 10
- Ensure that the voltage and polarity of the power source is correct. Power Controller RS422/ RS485 RS232 24V DC 24V DC Ethernet 5. Carefully remove the laminated film over the operator panel display, to avoid static electricity that could damage the panel. Mitsubishi Electric, MA00818C...
2.2.3 Other Connections and Peripherals Cables, peripheral equipment and accessories must be suitable for the application and its environment. For further details or recommendations, please refer to the supplier. Mitsubishi Electric, MA00818C...
UL and cUL: The power supply must conform with the requirements for class II power supplies. Ambient Vertical installation: 0 ° to +50 °C temperature Horizontal installation: 0 ° to +40 °C -20 ° to +70 °C Storage temperature Mitsubishi Electric, MA00818C...
Page 14
UL, cUL UL 1604 Class I, Div 2 / UL 508 / UL 50 4x indoor use only approvals (when product or packing is marked) NEMA 4x indoor use only * See section Chemical Resistance for more information. Mitsubishi Electric, MA00818C...
Autoflex EB withstands exposure to the same chemicals as Autotex F157 or F207 according to section Autotex F157/F207. Outdoor Use In common with all polyester based films Autoflex EB is not suitable for use in conditions of long term exposure to direct sunlight. Mitsubishi Electric, MA00818C...
Multi-wire conductors are better than single wire conductors with the same area. A braided conductor wire with the same area is even better. The best is a short, thick grounding braid. Mitsubishi Electric, MA00818C...
4. A more elegant method is to expand the shielded Ethernet cabling with a piece of unshielded Ethernet cable. 5. You can ground the shield via an external 0.1 uF/250 V plastic capacitor. This will connect the HF transients to the ground. Mitsubishi Electric, MA00818C...
– Ferrite cores that are snapped onto the shielded cabling may remove minor distur- bances. Large ferrite pieces that are snapped onto unshielded cabling and where the wires go 2-4 times around the cores are approximately 5-25 times more effi- cient. Mitsubishi Electric, MA00818C...
The loss effect drops from e.g. 25 W to only 5 W. The operator panel’s loss effect = supply voltage x current. Virtually no power goes to external users and no loss effects due to inputs. Mitsubishi Electric, MA00818C...
–Transients on the 24 V feed are connected to the ground. –No risk that the 24 V feed is at a high level in relationship to the ground. This is not unusual since there is high static electricity. Mitsubishi Electric, MA00818C...
Page 24
24 V feed, disturbances and grounding currents from the 0 V on the 24 V side will disrupt communication. Using this type of unit solves one problem but creates a larger problem! A substandard installation may work now, but problems may arise when other devices are connected. Mitsubishi Electric, MA00818C...
3. Connect two 1k/0.25 W resistors in the 25-pole D-sub contact. Set jumper pins 6-19. 4. Use CAB8. It offers the option of bus termination with pull-up/-down. It is also easy to connect the bus cable via the screw terminal block. Mitsubishi Electric, MA00818C...
Page 26